2011-11-15 09:35:002223 PALM BEACH LAKES BOULEVARD
 PERMIT #11090530
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 NOTE: CONTRACTOR IS PROCEEDING AT OWN RISK AS MASTER
 PERMIT (#11110177 ) HAS NOT BEEN ISSUED.
  
 INDICATE THE CANDELA RATING OF EACH VISUAL APPLIANCE.
  
 ENTIRE FIRE ALARM SYSTEM SHALL BE UL (OR EQUAL)
 CERTIFICATED FOR CENTRAL STATION SERVICE BY FINAL FIRE
 INSPECTION.
  
 TO MEET THE AUDIBILITY REQUIREMENTS OF NFPA 72, THE
 FIRE ALARM SYSTEM NEEDS TO BE INTEGRATED WITH THE
 BUILDING SOUND SYSTEM TO CUT POWER TO THE NON-FIRE
 ALARM SPEAKERS IN AN ALARM CONDITION.
  
 FIRE ALARM FLOOR PLAN NEEDS TO BE UPDATED TO THE NEW
 FLOOR PLAN PER THE MASTER PERMIT #11110177. ADDITIONAL
 NOTIFICATION APPLIANCES AND A PULL STATION WILL NEED TO
 BE ADDED BASED UPON NEW FLOOR PLAN.
  
 UPDATE VOLTAGE DROP AND BATTERY CALCULATIONS TO BREAK
 DOWN THE QUANTITY OF DEVICES. CURRENT CALCULATIONS ONLY
 INDICATE 1 DEVICE. INDICATE THE SIZE OF THE EXISTING
 BATTERY POWER SUPPLY.
  
 PROVIDE A PRE-RECORDED FIRE ALARM EVACUATION MESSAGE
 NOTIFYING OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN
 THE BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE
 BUILDING IMMEDIATELY. INDICATE THE EXACT MESSAGE ON THE
 PLANS.
  
 INDICATE LOCATION OF NEW REMOTE ANNUNCIATOR.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW