 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ADDRESS ON PLANS DOES NOT MATCH THE ADDRESS ON THE
 PERMIT APPLICATION.
  
 NO DRAWING SCALE PROVIDED.
  
 NO VOLTAGE DROP OR BATTERY CALCULATIONS PROVIDED.
  
 PER LOCAL CODE AMENDMENTS, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 NO OCCUPANCY TYPE INDICATED ON THE PLANS.
  
 NOTIFICATION APPLIANCES IN RESTROOMS NOT PROVIDED WITH
 IDENTIFICATION NUMBER.
  
 INDICATE IF THE EXISTING CRICUITS ARE BEING EXTENDED
 INTO THE NEW AREAS OR IF NEW CIRCUITS ARE BEING
 PROVIDED.
  
 INDICATE THE CANDELA RATING OF EACH VISUAL APPLIANCE.
  
 INDICATE THE CLASS AND STYLE OF WIRING.
  
 THE LOCATIONS OF THE NOTIFICATION APPLIANCES APPEAR TO
 BE GROSSLY OVERSPACED.
  
 ADDING NOTIFICATION APPLIANCES WILL INCREASE THE JOB
 VALUE BEYOND $5,000 AND WILL REQUIRE A PROFESSIONAL
 ENGINEER TO SIGN AND SEAL THE PLANS.
  
 THE AREA INDICATED AS "EVENT HALL ADDITION" ALREADY
 APPEARS TO BE PART OF AN EXISTING APPLIED FOR PERMIT
 (#11070070). SUB-PERMITS ARE GENERALLY NOT ISSUED
 BEFORE MASTER BUILDING PERMITS.
  