2011-11-02 13:14:29ROOFING RE-SUBMITTAL CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- ENGINEER DOING THE RAS 117 CALCULATIONS NEEDS TO
 REVISE THE FLAT ROOF BASE FASTENING SPACING FOR ZONE #2
 (PERIMETER AREA). ACCORDING TO SEC. 10.4.5 OF RAS 117,
 ALL FRACTIONS SHALL BE ROUNDED DOWN TO THE NEXT WHOLE
 NUMBER. ENGINEER SPECIFIES FASTENER SPACING AT 7.5".
 REVISE AS REQUIRED. NEED TO ROUND DOWN TO THE NEXT
 WHOLE NUMBER.
  
 2- ALL PRODUCT APPROVALS (METAL ROOFING AND FLAT ROOF
 ASSEMBLY) NEED TO BE REVIEWED AND APPROVED IN WRITING
 (NOT SIGNING AND SEALING) BY THE ENGINEER OF RECORD AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. SUBMIT
 ALL PRODUCT APPROVALS WITH THE ENGINEER'S OF RECORD
 APPROVAL.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER