Plan Review Notes
Plan Review Notes For Permit 11090496
Permit Number 11090496
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-09-29 13:46:39801 NORTHPOINT PARKWAY - SUITE #1
 PERMIT #11090496
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE NEW FIRE RATED DOOR PROVIDED IN THE 1-HOUR FIRE
 BARRIER OF CONFERENCE ROOM #10 SHOULD BE A 45-MINUTE
 FIRE RATED DOOR, NOT A 20-MINUTE FIRE RATED DOOR.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 SHEET E-2: THE DOOR TO CONFERENCE ROOM #10 IS SHOWN AS
 AN EXIT DOOR, VERIFY THIS DOOR IS NOT SUBJECT TO
 LOCKING.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  