Date Text
2011-10-28 12:07:464325 NORTH HAVERHILL ROAD
 PERMIT #11090479
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 **COMMENTS WERE RESPONDED TO BY TELEPHONE CONVERSATION
 WITH JACKIE MICHELS ON 10/28/11 AT 12:00**
  
 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE A SURFACE
 DESIGNED TO ACCOMMODATE FIRE APPARATUS WEIGHING AT
 LEAST 32 TONS. ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED
 WIDTH OF NOT LESS THAN 20 FEET AND AN UNOBSTRUCTED
 VERTICAL CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES
 PER SECTION 18.2.3.4.1.1 OF THE FLORIDA FIRE PREVENTION
 CODE - NFPA 1 UNIFORM FIRE CODE.
 RESPONSE: EXISTING ACCESS ROADS ARE PROVIDED ADJACENT
 TO THE DELIVERY DRIVE ROAD.
  
 PROVIDE LISTED SECONDARY CONTAINMENT TANKS FOR LIQUID
 CHLORINE OR PROVIDE SPILL CONTROL AND SECONDARY
 CONTAINMENT FOR BUILDINGS STORING HAZARDOUS MATERIALS
 LIQUIDS IN EXCESS OF 55 GALLONS PER SECTION 60.3.2.8.2
 AND SECTION 60.3.2.8.3 OF FFPC - NFPA 1.
 RESPONSE: TANKS WILL BE DOUBLE-WALLED CONTAINMENT
 TANKS.
  
 PROVIDE TWO MEANS OF EGRESS FROM EACH BUILDING WHEN THE
 BUILDING SIZE EXCEEDS 200 SQUARE FEET PER SECTION
 60.3.2.4.3 OF FFPC - NFPA 1.
 RESPONSE: BUILDINGS WILL BE LESS THAN 100 SQUARE FEET.
  
 SOME SHEETS REFERENCE THE TANKS AS STORING SODIUM
 HYPOCHLORITE WHILE OTHER SHEETS INDICATE PURE CHLORINE.
 PLEASE CLARIFY WHAT MATERIAL WILL BE STORED.
 RESPONSE: CHEMICAL COMPOSITION WILL BE SODIUM
 HYPOCHLORITE CONSISTING OF 12% CHLORINE. AT 12%
 CHLORINE IS NOT DEEMED AN OXIDIZER.
  
 BUILDINGS CONTAINING HAZARDOUS MATERIALS TO BE
 IDENTIFIED WITH DIAMOND PLACARD INDICATING HEALTH,
 FLAMMABILITY AND REACTIVITY RATINGS PER NFPA 704.
 RESPONSE: DIAMOND PLACARDS WILL BE PROVIDED.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW


Account Summary | Usage Policy | Privacy Policy