Plan Review Notes
Plan Review Notes For Permit 11090479
Permit Number 11090479
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-10-04 15:12:124325 NORTH HAVERHILL ROAD
 PERMIT #11090479
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE A SURFACE
 DESIGNED TO ACCOMMODATE FIRE APPARATUS WEIGHING AT
 LEAST 32 TONS. ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED
 WIDTH OF NOT LESS THAN 20 FEET AND AN UNOBSTRUCTED
 VERTICAL CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES
 PER SECTION 18.2.3.4.1.1 OF THE FLORIDA FIRE PREVENTION
 CODE ? NFPA 1 UNIFORM FIRE CODE.
  
 PROVIDE LISTED SECONDARY CONTAINMENT TANKS FOR LIQUID
 CHLORINE OR PROVIDE SPILL CONTROL AND SECONDARY
 CONTAINMENT FOR BUILDINGS STORING HAZARDOUS MATERIALS
 LIQUIDS IN EXCESS OF 55 GALLONS PER SECTION 60.3.2.8.2
 AND SECTION 60.3.2.8.3 OF FFPC - NFPA 1.
  
 PROVIDE TWO MEANS OF EGRESS FROM EACH BUILDING WHEN THE
 BUILDING SIZE EXCEEDS 200 SQUARE FEET PER SECTION
 60.3.2.4.3 OF FFPC - NFPA 1.
  
 SOME SHEETS REFERENCE THE TANKS AS STORING SODIUM
 HYPOCHLORITE WHILE OTHER SHEETS INDICATE PURE CHLORINE.
 PLEASE CLARIFY WHAT MATERIAL WILL BE STORED.
  
 BUILDINGS CONTAINING HAZARDOUS MATERIALS TO BE
 IDENTIFIED WITH DIAMOND PLACARD INDICATING HEALTH,
 FLAMMABILITY AND REACTIVITY RATINGS PER NFPA 704.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  