| Plan Review Notes For Permit 11090473 |
| Permit Number |
11090473 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-09-22 12:30:44 | 801 SOUTH OLIVE AVENUE - UNITS #806/#807 | | | PERMIT #11090473 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | ELIMINATE ALL SHEET REFERENCES TO NFPA 13R AS THIS | | | STANDARD CAN ONLY BE UTILIZED FOR RESIDENTIAL BUILDINGS | | | UP TO FOUR STORIES IN HEIGHT. SPRINKLER DESIGN SHALL | | | CONFORM TO NFPA 13 WITH THE USE OF RESIDENTIAL | | | SPRINKLERS WITHIN DWELLING UNITS. | | | | | | SPRINKLER PROTECTION IS REQUIRED IN ALL CLOSET SPACES. | | | THE EXCEPTION TO NOT LOCATE SPRINKLERS IN SMALL CLOSETS | | | 24 SQUARE FEET OR SMALLER ONLY PERTAINS TO HOTEL/MOTEL | | | OCCUPANCIES. | | | | | | THE DISTANCE BETWEEN TWO PENDENT SPRINKLERS IN THE | | | LIVING/SALON ROOM EXCEEDS 18 FEET. | | | | | | SPRINKLER COVERAGE APPEARS INADEQUATE BETWEEN THE | | | FAMILY KITCHEN AND PANTRY DOOR AREA. | | | | | | PROVIDE CEILING AND SOFFIT HEIGHTS ON PLANS. | | | | | | THE HANGER SPACING CHART SHOWS DISTANCES FOR SYSTEM | | | PRESSURES LESS THAN 100 PSI. REVISE CHART FOR SYSTEM | | | PRESSURE EXCEEDING 100 PSI. | | | | | | INDICATE THE METHOD TO BE USED TO PREVENT UPWARD | | | MOVEMENT OF PENDENT SPRINKLERS SUPPORTED WITH STANDARD | | | BAND HANGERS. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|