Plan Review Notes
Plan Review Notes For Permit 11090467
Permit Number 11090467
Review Stop M
Sequence Number 2
Notes
Date Text
2012-03-26 16:58:142007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) THE MECHANICAL PLANS ON SHEET A-5.0 HAVE THE TITLE
 BLOCK OF THE ARCHITECT ON THEM AND ARE NOT SIGNED AND
 SEALED BY HIM AS REQUIRED BY FLORIDA STATUTES SECTION
 481 AND F.A.C.61G1-16.004. THE MECHANICAL PLANS DO NOT
 HAVE TO BE DESIGNED BY AN ARCHITECT OR ENGINEER. THE
 MECHANICAL CONTRACTOR CAN DESIGN THE SYSTEM AND PROVIDE
 HIS NAME AND LICENSE NUMBER AND CONTACT NUMBER ON THE
 PLAN. THE ARCHITECT'S TITLE BLOCK MUST BE REMOVED FROM
 THE MECHANICAL PLANS IF HE IS NOT TAKING DESIGN
 RESPONSIBILITY BY SIGNING AND SEALING THEM.
  
 2) THE DUCTWORK SPECIFIED TO BE INSTALLED UNDER THE
 HOUSE SHALL NOT BE LOCATED WITHIN 4 INCHES OF THE EARTH
 IN ACCORDANCE WITH FBCR M1601.3.10.
  
 3) SECTION N 1100.0 REQUIRES ENERGY CALCULATIONS FOR
 THE NEW BONUS ROOM ABOVE THE GARAGE. THE ELECTRICAL
 PLANS INDICATE THAT IT HAS BEEN DESIGNED TO ACCOMMODATE
 THE FUTURE INSTALLATION OF HEATING OR COOLING
 EQUIPMENT.
  
 4) THE ENERGY CALC. FORMS ARE REQUIRED TO BE SIGNED BY
 THE OWNER/AGENT. 2007 FBC ENERGY GLITCH AMENDMENTS
 N1100.2.2.
  
 5) SHOW COMPLIANCE WITH FBC M1701.1 FOR COMBUSTION AIR
 FOR THE GAS WATER HEATER AND DRYER IN THE SECOND FLOOR
 LAUNDRY ROOM. THE GAS RISER SHOWS THE WATER HEATER IS
 199,000 BTU AND THE DRYER IS 25,000 BTU. IN ORDER FOR
 ALL AIR FROM INSIDE THE BUILDING TO BE USED THE VOLUME
 OF THE SPACE CONTAINING THE FUEL BURNING EQUIPMENT IS
 REQUIRED TO BE GREATER THAN 50 CUBIC FEET PER 1,000
 BTU. THE LAUNDRY ROOM IS TOO SMALL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW