| 2012-03-26 16:58:14 | 2007 FBC W/2009 REVISIONS |
| | |
| | DENIED BY MECHANICAL |
| | |
| | 1) THE MECHANICAL PLANS ON SHEET A-5.0 HAVE THE TITLE |
| | BLOCK OF THE ARCHITECT ON THEM AND ARE NOT SIGNED AND |
| | SEALED BY HIM AS REQUIRED BY FLORIDA STATUTES SECTION |
| | 481 AND F.A.C.61G1-16.004. THE MECHANICAL PLANS DO NOT |
| | HAVE TO BE DESIGNED BY AN ARCHITECT OR ENGINEER. THE |
| | MECHANICAL CONTRACTOR CAN DESIGN THE SYSTEM AND PROVIDE |
| | HIS NAME AND LICENSE NUMBER AND CONTACT NUMBER ON THE |
| | PLAN. THE ARCHITECT'S TITLE BLOCK MUST BE REMOVED FROM |
| | THE MECHANICAL PLANS IF HE IS NOT TAKING DESIGN |
| | RESPONSIBILITY BY SIGNING AND SEALING THEM. |
| | |
| | 2) THE DUCTWORK SPECIFIED TO BE INSTALLED UNDER THE |
| | HOUSE SHALL NOT BE LOCATED WITHIN 4 INCHES OF THE EARTH |
| | IN ACCORDANCE WITH FBCR M1601.3.10. |
| | |
| | 3) SECTION N 1100.0 REQUIRES ENERGY CALCULATIONS FOR |
| | THE NEW BONUS ROOM ABOVE THE GARAGE. THE ELECTRICAL |
| | PLANS INDICATE THAT IT HAS BEEN DESIGNED TO ACCOMMODATE |
| | THE FUTURE INSTALLATION OF HEATING OR COOLING |
| | EQUIPMENT. |
| | |
| | 4) THE ENERGY CALC. FORMS ARE REQUIRED TO BE SIGNED BY |
| | THE OWNER/AGENT. 2007 FBC ENERGY GLITCH AMENDMENTS |
| | N1100.2.2. |
| | |
| | 5) SHOW COMPLIANCE WITH FBC M1701.1 FOR COMBUSTION AIR |
| | FOR THE GAS WATER HEATER AND DRYER IN THE SECOND FLOOR |
| | LAUNDRY ROOM. THE GAS RISER SHOWS THE WATER HEATER IS |
| | 199,000 BTU AND THE DRYER IS 25,000 BTU. IN ORDER FOR |
| | ALL AIR FROM INSIDE THE BUILDING TO BE USED THE VOLUME |
| | OF THE SPACE CONTAINING THE FUEL BURNING EQUIPMENT IS |
| | REQUIRED TO BE GREATER THAN 50 CUBIC FEET PER 1,000 |
| | BTU. THE LAUNDRY ROOM IS TOO SMALL. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |