| 2011-12-01 07:48:35 | 2007 FBC W/2009 REVISIONS |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) ALL OF THE PLANS FROM THE ARCHITECT AND ENGINEER |
| | WITH THEIR TITLE BLOCKS ARE REQUIRED TO BE SIGNED AND |
| | SEALED IN ACCORDANCE WITH FAC 61G1-16.001 AND FAC |
| | 61G15-23.002. |
| | |
| | 2) SHOW LOCATION OF SMOKE ALARM AND CARBON MONOXIDE |
| | DETECTOR IN THE BONUS ROOM AS REQUIRED BY FBC R313.2.1 |
| | AND R313.4. |
| | |
| | 3) SPECIFY THE TOTAL OF ADDITIONAL LIVING AREA ON THE |
| | PLANS. CITY AMENDMENTS FBC 106.1.2 |
| | |
| | 4) ON SHEET A-0.0 UNDER CODE SUMMARY, THE BOCA RATON |
| | CITY AMENDMENTS ARE SPECIFIED RATHER THAN THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. PLEASE CORRECT. |
| | |
| | 5) ON SHEET A-0.0 UNDER CODE SUMMARY, THE OCCUPANCY IS |
| | SPECIFIED AS R1A RATHER THAN R3. PLEASE CORRECT. SEE |
| | FBC 310.1. |
| | |
| | 6) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE TWO |
| | STORY DWELLING UNIT AND THE BONUS ROOM ABOVE THE GARAGE |
| | AS REQUIRED BY THE 2007 FBC ENERGY AMENDMENTS SECTION |
| | N1100.3. |
| | |
| | 7) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE |
| | ROOFING MATERIALS, COR-A-VENTS, GARAGE DOORS, STORM |
| | SHUTTERS AND OTHER EXTERIOR COMPONENTS AND CLADDING AS |
| | REQUIRED BY DCA RULE 9N-3. CITY AMENDMENT FBC 106.3.3 |
| | REQUIRES PRODUCT APPROVALS TO BE REVIEWED AND APPROVED |
| | IN WRITING BY THE DESIGNER OF RECORD. ONLY ONE COPY OF |
| | THE WINDOW AND DOOR PRODUCT APPROVALS WERE SUBMITTED. |
| | THE DOOR SCHEDULE ON SHEET A-3.0 OF THE PLANS SPECIFIES |
| | NOA NO. 09-1028.10 FOR THE FRENCH DOORS, HOWEVER, THE |
| | ONE THAT WAS SUBMITTED AND APPROVED BY HISTORIC REVIEW |
| | IS NOA NO. 07-0629.10. |
| | |
| | 8) SUBMIT TWO SETS OF STRUCTURAL DRAWINGS FOR THE |
| | PROPOSED WORK. INCLUDE WALL SECTION FROM FOUNDATION |
| | THROUGH ROOF ( INCLUDING ASSEMBLY AND MATERIALS), |
| | CONNECTOR TABLES AND WIND REQUIREMENTS. CITY AMENDMENTS |
| | FBC 106.3.5.4 |
| | |
| | 9) PROVIDE TWO SETS OF FOUNDATION PLANS, FIRST AND |
| | SECOND FLOOR FRAMING PLAN AND ROOF FRAMING PLAN. CITY |
| | AMENDMENTS FBC 106.1.1 AND 106.1.1.2 |
| | |
| | 10) SPECIFY THE REQUIRED OPENING PRESSURES ON THE |
| | PLANS. |
| | |
| | 11) SPECIFY THE ROOF AND WALL SHEATHING FASTENING |
| | REQUIREMENTS ON THE PLANS. FBC R602.3 AND R803.2.3.1 |
| | |
| | 12) PROVIDE WINDOW AND DOOR BUCK FASTENING |
| | REQUIREMENTS. FBC R613.6.1.1 |
| | |
| | 13) SHOW COMPLIANCE WITH FBC R 408.3 AND R408.4 FOR |
| | CRAWL SPACE VENTILATION AND ACCESS. |
| | |
| | 14) SHOW COMPLIANCE WITH FBC R 703.6.2 AND ASTM C 1063 |
| | SECTION 7.11.5 WHICH REQUIRES A FOUNDATION WEEP SCREED |
| | AT THE BOTTOM OF ALL FRAMED EXTERIOR WALLS, BELOW THE |
| | FLOOR LINE. |
| | |
| | 15) SPECIFY THE DESIGN CRITERIA ON THE PLANS IN |
| | ACCORDANCE WITH R301.2.1.1. SPECIFY THE WIND SPEED, |
| | EXPOSURE CATEGORY, DESIGN PRESSURES, REQUIRED SOIL |
| | BEARING CAPACITY, ROOF AND FLOOR LOADS, ETC. |
| | |
| | 16) THE WINDOWS IN UPSTAIRS BEDROOMS 2 AND 3 DO NOT |
| | COMPLY WITH FBC R310 FOR EMERGENCY ESCAPE AND RESCUE |
| | CLEAR OPENING SIZES. PLEASE CORRECT. |
| | |
| | 17) THE GAS WATER HEATER IN THE UPSTAIRS MASTER BEDROOM |
| | W.I.C. IS IN A PROHIBITED LOCATION ACCORDING TO FBCR |
| | G2406.2 (303.3) . SHOW COMPLIANCE WITH G2406.2 ON THE |
| | PLANS. |
| | |
| | 18) SHOW HOW THE REQUIREMENTS OF FBCR SECTION G2407 |
| | (304) FOR COMBUSTION, VENTILATION AND DILUTION AIR FOR |
| | THE GAS APPLIANCES WILL BE MET. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |