2011-12-01 07:48:352007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) ALL OF THE PLANS FROM THE ARCHITECT AND ENGINEER
 WITH THEIR TITLE BLOCKS ARE REQUIRED TO BE SIGNED AND
 SEALED IN ACCORDANCE WITH FAC 61G1-16.001 AND FAC
 61G15-23.002.
  
 2) SHOW LOCATION OF SMOKE ALARM AND CARBON MONOXIDE
 DETECTOR IN THE BONUS ROOM AS REQUIRED BY FBC R313.2.1
 AND R313.4.
  
 3) SPECIFY THE TOTAL OF ADDITIONAL LIVING AREA ON THE
 PLANS. CITY AMENDMENTS FBC 106.1.2
  
 4) ON SHEET A-0.0 UNDER CODE SUMMARY, THE BOCA RATON
 CITY AMENDMENTS ARE SPECIFIED RATHER THAN THE CITY OF
 WEST PALM BEACH AMENDMENTS. PLEASE CORRECT.
  
 5) ON SHEET A-0.0 UNDER CODE SUMMARY, THE OCCUPANCY IS
 SPECIFIED AS R1A RATHER THAN R3. PLEASE CORRECT. SEE
 FBC 310.1.
  
 6) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE TWO
 STORY DWELLING UNIT AND THE BONUS ROOM ABOVE THE GARAGE
 AS REQUIRED BY THE 2007 FBC ENERGY AMENDMENTS SECTION
 N1100.3.
  
 7) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 ROOFING MATERIALS, COR-A-VENTS, GARAGE DOORS, STORM
 SHUTTERS AND OTHER EXTERIOR COMPONENTS AND CLADDING AS
 REQUIRED BY DCA RULE 9N-3. CITY AMENDMENT FBC 106.3.3
 REQUIRES PRODUCT APPROVALS TO BE REVIEWED AND APPROVED
 IN WRITING BY THE DESIGNER OF RECORD. ONLY ONE COPY OF
 THE WINDOW AND DOOR PRODUCT APPROVALS WERE SUBMITTED.
 THE DOOR SCHEDULE ON SHEET A-3.0 OF THE PLANS SPECIFIES
 NOA NO. 09-1028.10 FOR THE FRENCH DOORS, HOWEVER, THE
 ONE THAT WAS SUBMITTED AND APPROVED BY HISTORIC REVIEW
 IS NOA NO. 07-0629.10.
  
 8) SUBMIT TWO SETS OF STRUCTURAL DRAWINGS FOR THE
 PROPOSED WORK. INCLUDE WALL SECTION FROM FOUNDATION
 THROUGH ROOF ( INCLUDING ASSEMBLY AND MATERIALS),
 CONNECTOR TABLES AND WIND REQUIREMENTS. CITY AMENDMENTS
 FBC 106.3.5.4
  
 9) PROVIDE TWO SETS OF FOUNDATION PLANS, FIRST AND
 SECOND FLOOR FRAMING PLAN AND ROOF FRAMING PLAN. CITY
 AMENDMENTS FBC 106.1.1 AND 106.1.1.2
  
 10) SPECIFY THE REQUIRED OPENING PRESSURES ON THE
 PLANS.
  
 11) SPECIFY THE ROOF AND WALL SHEATHING FASTENING
 REQUIREMENTS ON THE PLANS. FBC R602.3 AND R803.2.3.1
  
 12) PROVIDE WINDOW AND DOOR BUCK FASTENING
 REQUIREMENTS. FBC R613.6.1.1
  
 13) SHOW COMPLIANCE WITH FBC R 408.3 AND R408.4 FOR
 CRAWL SPACE VENTILATION AND ACCESS.
  
 14) SHOW COMPLIANCE WITH FBC R 703.6.2 AND ASTM C 1063
 SECTION 7.11.5 WHICH REQUIRES A FOUNDATION WEEP SCREED
 AT THE BOTTOM OF ALL FRAMED EXTERIOR WALLS, BELOW THE
 FLOOR LINE.
  
 15) SPECIFY THE DESIGN CRITERIA ON THE PLANS IN
 ACCORDANCE WITH R301.2.1.1. SPECIFY THE WIND SPEED,
 EXPOSURE CATEGORY, DESIGN PRESSURES, REQUIRED SOIL
 BEARING CAPACITY, ROOF AND FLOOR LOADS, ETC.
  
 16) THE WINDOWS IN UPSTAIRS BEDROOMS 2 AND 3 DO NOT
 COMPLY WITH FBC R310 FOR EMERGENCY ESCAPE AND RESCUE
 CLEAR OPENING SIZES. PLEASE CORRECT.
  
 17) THE GAS WATER HEATER IN THE UPSTAIRS MASTER BEDROOM
 W.I.C. IS IN A PROHIBITED LOCATION ACCORDING TO FBCR
 G2406.2 (303.3) . SHOW COMPLIANCE WITH G2406.2 ON THE
 PLANS.
  
 18) SHOW HOW THE REQUIREMENTS OF FBCR SECTION G2407
 (304) FOR COMBUSTION, VENTILATION AND DILUTION AIR FOR
 THE GAS APPLIANCES WILL BE MET.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]