| Plan Review Notes For Permit 11090451 |
| Permit Number |
11090451 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-09-21 09:18:08 | PLEASE INICATE ON THE PLAN TEH FOLLOWING: NEC 215.5, | | | NEC T 300.5, 300.5(D) 3 | | | | | | 1. SIZE OF THE CONDUIT | | | 2. BURIAL DEPTH | | | 3. WARNING RIBBON REQUIRED 12 INCHES ABOVE SERVICE | | | CONDUIT | | | | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | |
|