Plan Review Notes
Plan Review Notes For Permit 11090382
Permit Number 11090382
Review Stop B
Sequence Number 1
Notes
Date Text
2011-09-19 09:59:042007 FBC W/2009 REVISIONS
  
 1) THE SITE SPECIFIC ENGINEERING FOR THE ANCHORS IS
 ADEQUATE. HOWEVER, THERE IS NOTHING IN THE PRODUCT
 APPROVAL WHICH INDICATES THAT THE BOTTOM TRACK IS
 CAPABLE OF RESISTING THE WIND LOADING BETWEEN ANCHORS
 THAT ARE SPACED 3' - 4" O.C. THEREFORE, INSTALL 2X
 BLOCKING BETWEEN THE JOIST SUCH THAT ADDITIONAL ANCHORS
 CAN BE INSTALLED REDUCING THE ANCHOR SPANS OR PROVIDE
 CALCULATIONS FOR THE TRACK WHICH SHOW IT IS CAPABLE OF
 RESISTING THE APPLICABLE LOADS WHEN THE ANCHORS ARE
 SPACED AT 3' - 4" O.C.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]