2011-09-15 10:04:31222 LAKEVIEW AVENUE - SUITE #900
 PERMIT #11090292
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT ADDITIONAL INFORMATION*****
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 STROKE. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER. REFERENCE SECTION 8.3.2.4 OF FLORIDA
 FIRE PREVENTION CODE - NFPA 101
  
 VERIFY NEW GLASS SIDE LIGHTS FOR DOOR #1 ARE FIRE
 RATED.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 SHEET E-2: NO EMERGENCY LIGHTING PROVIDED AT ENTRY
 #900. VERIFY ADJACENT EMERGENCY LIGHT PROVIDES ONE FOOT
 CANDLE AT FRONT ENTRY.
  
 SHEET E-2: NO FIRE ALARM NOTIFICATION APPLIANCES SHOWN
 ON PLAN.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW