| 2011-09-19 15:22:50 | 11090292 | | | 222 LAKEVIEW AVE #900 | | | INTERIOR RENOVATION | | | | | | LOCATE PANEL BOARDS AND TRANSFORMER ON THE FLOOR PLAN. | | | PROVIDE SUPPORT DETAIL FOR TRANSFORMER IF CEILING | | | MOUNTED. SHOW SAFE WORKING CLEARANCES. UPDATE PANEL | | | SCHEDULES AND RISER TO SHOW ALL FEEDERS. INCLUDE PANEL | | | " L" LOAD IN SCHEDULE FOR PANEL "H". NEC 215.5, 110.26 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|