Plan Review Notes
Plan Review Notes For Permit 11090291
Permit Number 11090291
Review Stop M
Sequence Number 1
Notes
Date Text
2011-09-16 11:16:19MECHANICAL PROVISO:
 1) SHEET M1 GENERAL NOTE # 14 SMOKE DETECTORS TO COMPLY
 WITH:
 606.2.1 SUPPLY AIR SYSTEMS. SMOKE DETECTORS SHALL BE
 INSTALLED IN SUPPLY AIR SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM (0.9 M3/S), IN THE SUPPLY AIR
 DUCT.
  
 EXCEPTION: SMOKE DETECTORS ARE NOT REQUIRED IN THE
 SUPPLY AIR SYSTEM WHERE THE SPACE SERVED BY THE AIR
 DISTRIBUTION SYSTEM IS PROTECTED BY A SYSTEM OF AREA
 SMOKE DETECTORS IN ACCORDANCE WITH THE FLORIDA FIRE
 PREVENTION CODE. THE AREA SMOKE DETECTOR SYSTEM SHALL
 COMPLY WITH SECTION 606.4.
  
 606.4.1 SUPERVISION. THE DUCT SMOKE DETECTORS SHALL BE
 CONNECTED TO A FIRE ALARM SYSTEM. THE ACTUATION OF A
 DUCT SMOKE DETECTOR SHALL ACTIVATE A VISIBLE AND
 AUDIBLE SUPERVISORY SIGNAL AT A CONSTANTLY ATTENDED
 LOCATION.
  
 EXCEPTIONS:
  
 1. THE SUPERVISORY SIGNAL AT A CONSTANTLY ATTENDED
 LOCATION IS NOT REQUIRED WHERE THE DUCT SMOKE DETECTOR
 ACTIVATES THE BUILDING'S ALARM-INDICATING APPLIANCES.
  
 2. IN OCCUPANCIES NOT REQUIRED TO BE EQUIPPED WITH A
 FIRE ALARM SYSTEM, ACTUATION OF A SMOKE DETECTOR SHALL
 ACTIVATE A VISIBLE AND AN AUDIBLE SIGNAL IN AN APPROVED
 LOCATION. DUCT SMOKE DETECTOR TROUBLE CONDITIONS SHALL
 ACTIVATE A VISIBLE OR AUDIBLE SIGNAL IN AN APPROVED
 LOCATION AND SHALL BE IDENTIFIED AS AIR DUCT DETECTOR
 TROUBLE.
  