Plan Review Notes
Plan Review Notes For Permit 11090275
Permit Number 11090275
Review Stop B
Sequence Number 1
Notes
Date Text
2011-09-14 07:57:032007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C,
 BECAUSE IT IS WITHIN 1500 FEET OF EXPOSURE C TERRAIN.
 SEE FBC R301.2.1.4.3.
  
 2) SUBMIT TWO SETS OF RAS 117 CALCULATIONS
 PREPARED,SIGNED AND SEALED BY A FLORIDA REGISTERED
 ENGINEER, ARCHITECT OR REGISTERED ROOF CONSULTANT FOR
 THE ENHANCED FASTENING OF THE BASE SHEET FOR THE
 CERTAINTEED MODIFIED ROOFING SYSTEM (NOA NO.
 08-0410.09) AS REQUIRED BY GENERAL LIMITATION #7 OF THE
 PRODUCT APPROVAL. DCA RULE 9N-3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW