2011-11-28 12:00:073654 GEORGIA AVENUE
 PERMIT #11090261
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DEMOLITION PLANS DO NOT INDICATE ANY SCOPE ASSOCIATED
 WITH THE EXISTING SECOND FLOOR/MEZZANINE AREA THAT WAS
 SHOWN ON THE ORIGINAL PERMIT APPLICATION DRAWINGS.
  
 THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY.
 INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE
 (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.2.1
 OF NFPA 101 FLORIDA EDITION 2006. CONFIRM EXISTING
 PARTITION (SEPARATING THE BUSINESS OCCUPANCY FROM THE
 FACTORY OCCUPANCY) IS A TWO-HOUR FIRE RATED SEPARATION.
  
 SHEET A0.1 INDICATES THE EXTERIOR DOOR ADJACENT TO
 OFFICE #140 IS NOT AN EXIT. SHEET E-1 INDICATES THIS
 DOOR IS AN EXIT.
  
 SHEET A1.1 REFLECTED CEILING PLAN GENERAL NOTE #4
 INDICATES THE BUILDING IS PROTECTED BY AN AUTOMATIC
 FIRE SPRINKLER SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW