| 2011-11-28 12:00:07 | 3654 GEORGIA AVENUE | | | PERMIT #11090261 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | DEMOLITION PLANS DO NOT INDICATE ANY SCOPE ASSOCIATED | | | WITH THE EXISTING SECOND FLOOR/MEZZANINE AREA THAT WAS | | | SHOWN ON THE ORIGINAL PERMIT APPLICATION DRAWINGS. | | | | | | THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY. | | | INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE | | | (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.2.1 | | | OF NFPA 101 FLORIDA EDITION 2006. CONFIRM EXISTING | | | PARTITION (SEPARATING THE BUSINESS OCCUPANCY FROM THE | | | FACTORY OCCUPANCY) IS A TWO-HOUR FIRE RATED SEPARATION. | | | | | | SHEET A0.1 INDICATES THE EXTERIOR DOOR ADJACENT TO | | | OFFICE #140 IS NOT AN EXIT. SHEET E-1 INDICATES THIS | | | DOOR IS AN EXIT. | | | | | | SHEET A1.1 REFLECTED CEILING PLAN GENERAL NOTE #4 | | | INDICATES THE BUILDING IS PROTECTED BY AN AUTOMATIC | | | FIRE SPRINKLER SYSTEM. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|