| Plan Review Notes For Permit 11090261 |
| Permit Number |
11090261 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-10-03 14:32:01 | 3654 GEORGIA AVENUE | | | PERMIT #11090261 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | SHEET A0.1 INDICATES THIS BUILDING IS TYPE IIB | | | CONSTRUCTION; HOWEVER, SHEET S1 INDICATES THE SECOND | | | FLOOR IS CONSTRUCTED OF WOODEN JOISTS. | | | | | | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH | | | EXIT SIGNS. | | | | | | STAIR DISCHARGES INSIDE THE BUILDING AT OFFICE #121. | | | EXITS SHALL TERMINATE DIRECTLY TO THE EXTERIOR UNLESS | | | THE DESIGN MEETS THE CRITERIA STATED IN SECTION 7.7 OF | | | THE LIFE SAFETY CODE - NFPA 101 FLORIDA EDITION. | | | | | | EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE | | | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING | | | FIRE/SMOKE BARRIER - PROTECT ALL OPENINGS. CHARACTERS | | | SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN | | | WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 | | | FEET ON CENTER. | | | | | | SHEET M -1: NO FIRE DAMPERS PROVIDED IN DUCTWORK | | | PENETRATING FIRE RATED STAIR ENCLOSURES. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|