2011-10-03 14:32:013654 GEORGIA AVENUE
 PERMIT #11090261
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A0.1 INDICATES THIS BUILDING IS TYPE IIB
 CONSTRUCTION; HOWEVER, SHEET S1 INDICATES THE SECOND
 FLOOR IS CONSTRUCTED OF WOODEN JOISTS.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 STAIR DISCHARGES INSIDE THE BUILDING AT OFFICE #121.
 EXITS SHALL TERMINATE DIRECTLY TO THE EXTERIOR UNLESS
 THE DESIGN MEETS THE CRITERIA STATED IN SECTION 7.7 OF
 THE LIFE SAFETY CODE - NFPA 101 FLORIDA EDITION.
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER - PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 SHEET M -1: NO FIRE DAMPERS PROVIDED IN DUCTWORK
 PENETRATING FIRE RATED STAIR ENCLOSURES.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  