| 2011-10-04 13:22:14 | BUILDING PLAN REVIEW |
| | PERMIT: 11090261 |
| | ADD: 3654 GEORGIA AVE |
| | CONT: PRINCE DEVELOPMENT GROUP |
| | TEL: (561)313-2818 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLEASE REVIEW A DISCREPANCY IN PLANS, SHEET A.01 |
| | BUILDING CODE SUMMARY INDICATES THE BUILDING AS A TYPE |
| | IIB UNPROTECTED/ NON-SPRIKLERED BUILDING, WHERE AS |
| | SHEET S1 INDICATES THE USE OF 2X WOOD JOIST FRAMING |
| | MEMEBERS. FBC-B 603.1.1 WILL NOT ALLOW THE USAGE OF ANY |
| | COMBUSTIBLE WOOD FLOOR JOIST, IT APPEARS THIS BUILDING |
| | WILL NEED TO BE RECLASSIFIED AND WILL NEED TO INDICATE |
| | TYPE OF BUILDING TYPE AND ALLOWABLE FRONTAGE INCREASES |
| | (FBC-B 506.2) TO QUALIFY FOR 29,026 SQ FT FOR THE FIRST |
| | FLOOR. |
| | |
| | 2) PLEASE REVIEW SHEET A0.2 THE FIRST FLOOR LOCATION |
| | FOR THE ACCESSIBLE LIFT INDICATES THIS AREA TO BE A |
| | EXISTING TEST KITCHEN. FBC-B 1014.2 (1) EGRESS SHALL |
| | NOT PASS THROUGH KITCHENS OR SIMILAR PURPOSES. PERMIT # |
| | 06100214 FOR 3624 GEORGIA AVE WERE FOR TOOJAY'S TEST |
| | KITCHEN SHEET A0.0 INDICATES THIS TO BE A TRAINING |
| | FACILITY WITH A SEATING AREA AS WELL, NOT JUST A |
| | KITCHEN, IT IS IMPORTANT TO NOTE ON THE PLANS THE |
| | LOCATION OF LIFT IS IN THE CUSTOMER SEATING AREA OF THE |
| | TRAINING FACILITY. PLEASE UPDATE THE PLAN TO REFLECT |
| | THE |
| | LIFT IS NOT ACTUALLY LOCATED IN A KITCHEN AS THE USAGE |
| | OF THIS AREA HAS NOT DEVIATED FROM WHAT WAS ORIGINALLY |
| | PERMITED. |
| | |
| | 3) AREA OF RESCUE ASSISTANCE WILL NEED TO COMPLY WITH: |
| | 3A) 11-4.3.11.4 TWO-WAY COMMUNICATION. A METHOD OF |
| | TWO-WAY COMMUNICATION, WITH BOTH VISIBLE AND AUDIBLE |
| | SIGNALS, SHALL BE PROVIDED BETWEEN EACH AREA OF RESCUE |
| | ASSISTANCE AND THE PRIMARY ENTRY. THE FIRE DEPARTMENT |
| | OR APPROPRIATE LOCAL AUTHORITY MAY APPROVE A LOCATION |
| | OTHER THAN THE PRIMARY ENTRY. |
| | |
| | 3B) 11-4.3.11.5 IDENTIFICATION. EACH AREA OF RESCUE |
| | ASSISTANCE SHALL BE IDENTIFIED BY A SIGN, WHICH STATES |
| | "AREA OF RESCUE ASSISTANCE" AND DISPLAYS THE |
| | INTERNATIONAL SYMBOL OF ACCESSIBILITY. THE SIGN SHALL |
| | BE ILLUMINATED WHEN EXIT SIGN ILLUMINATION IS REQUIRED. |
| | SIGNAGE SHALL ALSO BE INSTALLED AT ALL INACCESSIBLE |
| | EXITS AND WHERE OTHERWISE NECESSARY TO CLEARLY INDICATE |
| | THE DIRECTION TO AREAS OF RESCUE ASSISTANCE. IN EACH |
| | AREA OF RESCUE ASSISTANCE, INSTRUCTIONS ON THE USE OF |
| | THE AREA UNDER EMERGENCY CONDITIONS SHALL BE POSTED |
| | ADJOINING THE TWO-WAY COMMUNICATION SYSTEM. |
| | |
| | 4) 712.6 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, |
| | SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL |
| | REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE |
| | EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY |
| | HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE |
| | ANY DECORATIVE CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE |
| | AND SMOKE BARRIER - PROTECT ALL OPENINGS." |
| | |
| | 5) SHEET M-1 PLANS INDICATE DUCT PENETRATING 1 HR FIRE |
| | RATED WALLS (STAIRWELL) PROVIDE COMPLIANCE WITH SECTION |
| | FBC-B 712.3.3 DUCTS AND AIR TRANSFER OPENINGS. |
| | PENETRATIONS OF FIRE-RESISTANCE-RATED WALLS BY DUCTS |
| | THAT ARE NOT PROTECTED WITH DAMPERS SHALL COMPLY WITH |
| | SECTIONS 712.2 THROUGH 712.3.1. DUCTS AND AIR TRANSFER |
| | OPENINGS THAT ARE PROTECTED WITH DAMPERS SHALL COMPLY |
| | WITH SECTION 716. |
| | |
| | 716.4 ACCESS AND IDENTIFICATION. FIRE AND SMOKE DAMPERS |
| | SHALL BE PROVIDED WITH AN APPROVED MEANS OF ACCESS, |
| | WHICH IS LARGE ENOUGH TO PERMIT INSPECTION AND |
| | MAINTENANCE OF THE DAMPER AND ITS OPERATING PARTS. THE |
| | ACCESS SHALL NOT AFFECT THE INTEGRITY OF |
| | FIRE-RESISTANCE-RATED ASSEMBLIES. THE ACCESS OPENINGS |
| | SHALL NOT REDUCE THE FIRE-RESISTANCE RATING OF THE |
| | ASSEMBLY. ACCESS POINTS SHALL BE PERMANENTLY IDENTIFIED |
| | ON THE EXTERIOR BY A LABEL HAVING LETTERS NOT LESS THAN |
| | 0.5 INCH (12.7 MM) IN HEIGHT READING: FIRE/SMOKE |
| | DAMPER, SMOKE DAMPER OR FIRE DAMPER. ACCESS DOORS IN |
| | DUCTS SHALL BE TIGHT FITTING AND SUITABLE FOR THE |
| | REQUIRED DUCT CONSTRUCTION. |
| | |
| | 716.5 WHERE REQUIRED. FIRE DAMPERS, SMOKE DAMPERS, |
| | COMBINATION FIRE/SMOKE DAMPERS AND CEILING RADIATION |
| | DAMPERS SHALL BE PROVIDED AT THE LOCATIONS PRESCRIBED |
| | IN SECTIONS 716.5.1 THROUGH 716.5.5 AND SECTION 716.6. |
| | WHERE AN ASSEMBLY IS REQUIRED TO HAVE BOTH FIRE DAMPERS |
| | AND SMOKE DAMPERS, COMBINATION FIRE/SMOKE DAMPERS OR A |
| | FIRE DAMPER AND A SMOKE DAMPER SHALL BE REQUIRED. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |