2012-02-29 14:12:302007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) (SHOW COMPLIANCE WITH FBC R317.1 FOR ONE HOUR FIRE
 RESISTANCE RATED FLOOR/CEILING ASSEMBLY SEPARATION
 BETWEEN THE TWO DWELLING UNITS. NOTE: HVAC DUCTWORK
 WILL REQUIRE DAMPERS IF PENETRATING THE FIRE RATED
 ASSEMBLY PER FBC R317.3.1.1.) A TENANT WALL SEPARATION
 DETAIL WAS PROVIDED ON SHEET T-1 OF THE REVISED PLANS.
 HOWEVER, THE TENANTS ARE SEPARATED BY A FLOOR CEILING
 ASSEMBLY. PROVIDE A LISTED ONE HOUR FIRE RATED
 FLOOR/CEILING ASSEMBLY DETAIL ON THE PLANS. INCLUDE THE
 LISTING NUMBER ON THE DETAIL. REPEAT COMMENT.
  
 NOTE: ONE DWELLING UNIT IS LOCATED ON THE FIRST FLOOR
 AND THE OTHER DWELLING UNIT IS LOCATED ON THE SECOND
 FLOOR. THE FLOOR/CEILING ASSEMBLY BETWEEN THE TWO UNITS
 IS REQUIRED TO BE A ONE HOUR FIRE RATED ASSEMBLY. THERE
 ARE NOT ANY WALLS BETWEEN (SEPARATING ) THE TWO
 DWELLING UNITS. SPECIFY THE 1 HOUR FIRE RATED
 FLOOR/CEILING ASSEMBLY LISTING NUMBER ON THE PLANS. THE
 DUCT WORK FOR THE FIRST FLOOR A/C WILL NEED TO BE
 INSTALLED BELOW THE RATED CEILING UNLESS FIRE DAMPERS
 ARE INSTALLED WHERE THE RATED CEILING IS PENETRATED.
  