| Plan Review Notes For Permit 11090198 |
| Permit Number |
11090198 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2012-02-29 14:12:30 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) (SHOW COMPLIANCE WITH FBC R317.1 FOR ONE HOUR FIRE | | | RESISTANCE RATED FLOOR/CEILING ASSEMBLY SEPARATION | | | BETWEEN THE TWO DWELLING UNITS. NOTE: HVAC DUCTWORK | | | WILL REQUIRE DAMPERS IF PENETRATING THE FIRE RATED | | | ASSEMBLY PER FBC R317.3.1.1.) A TENANT WALL SEPARATION | | | DETAIL WAS PROVIDED ON SHEET T-1 OF THE REVISED PLANS. | | | HOWEVER, THE TENANTS ARE SEPARATED BY A FLOOR CEILING | | | ASSEMBLY. PROVIDE A LISTED ONE HOUR FIRE RATED | | | FLOOR/CEILING ASSEMBLY DETAIL ON THE PLANS. INCLUDE THE | | | LISTING NUMBER ON THE DETAIL. REPEAT COMMENT. | | | | | | NOTE: ONE DWELLING UNIT IS LOCATED ON THE FIRST FLOOR | | | AND THE OTHER DWELLING UNIT IS LOCATED ON THE SECOND | | | FLOOR. THE FLOOR/CEILING ASSEMBLY BETWEEN THE TWO UNITS | | | IS REQUIRED TO BE A ONE HOUR FIRE RATED ASSEMBLY. THERE | | | ARE NOT ANY WALLS BETWEEN (SEPARATING ) THE TWO | | | DWELLING UNITS. SPECIFY THE 1 HOUR FIRE RATED | | | FLOOR/CEILING ASSEMBLY LISTING NUMBER ON THE PLANS. THE | | | DUCT WORK FOR THE FIRST FLOOR A/C WILL NEED TO BE | | | INSTALLED BELOW THE RATED CEILING UNLESS FIRE DAMPERS | | | ARE INSTALLED WHERE THE RATED CEILING IS PENETRATED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|