2012-01-10 12:22:3111090198
 2212 FLORIDA AVE.
 RESIDENTIAL ADDITION
  
 SHOW LOCATION OF THE NEW SERVICE. NEC 215.15
 THE REQUIRED INTERSYSTEM BONDING STRIP NEEDS TO BEEN
 SHOWN ON THE SERVICE RISER PLAN. NEC 250.94
 MAIN ELECTRICAL DISCONNECTS MUST BE SERVICE RATED AND
 GROUPED IN ONE LOCATION. THE DRAWING IS UNCLEAR AS TO
 HOW THE TWO METERS AND RISERS FUNCTION. A BUILDING
 SHOULD ONLY HAVE ONE POINT OF SERVICE. NEC 230.2,
 230.40
 AT LEAST ONE GFCI PROTECTED RECEPTACLE IS REQUIRED
 OUTSIDE FRONT AND BACK. NEC 210.70
 ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2
 FEET IN WIDTH HAVE A RECEPTACLE (LIVING ROOM 2ND
 FLOOR). NEC 210.52
 THE ELECTRICAL PANEL MAY NOT BE LOCATED IN A BATHROOM.
 NEC 240.24
  