Plan Review Notes
Plan Review Notes For Permit 11090198
Permit Number 11090198
Review Stop B
Sequence Number 2
Notes
Date Text
2012-01-20 16:36:422007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) (SHOW COMPLIANCE WITH FBC R317.1 FOR ONE HOUR FIRE
 RESISTANCE RATED FLOOR/CEILING ASSEMBLY SEPARATION
 BETWEEN THE TWO DWELLING UNITS. NOTE: HVAC DUCTWORK
 WILL REQUIRE DAMPERS IF PENETRATING THE FIRE RATED
 ASSEMBLY PER FBC R317.3.1.1.) A TENANT WALL SEPARATION
 DETAIL WAS PROVIDED ON SHEET T-1 OF THE REVISED PLANS.
 HOWEVER, THE TENANTS ARE SEPARATED BY A FLOOR CEILING
 ASSEMBLY. PROVIDE A LISTED ONE HOUR FIRE RATED
 FLOOR/CEILING ASSEMBLY DETAIL ON THE PLANS. INCLUDE THE
 LISTING NUMBER ON THE DETAIL.
  
 2) (THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 STRUCTURAL MULLIONS HAVE INCOMPLETE DRAWINGS. SUBMIT
 COMPLETE LEGIBLE DRAWINGS. DCA RULE 9N-3) THE NOA
 DRAWINGS ARE BEING CUT OFF WHEN PRINTED. IN ORDER FOR
 THE COMPLETE PRODUCT APPROVAL DRAWINGS TO PRINT YOU
 WILL NEED TO SHRINK THEM TO FIT ON THE 8-1/2 X 11 PAPER
 OR USE LARGER PAPER.
  
 3) (PRODUCT APPROVALS WERE SUBMITTED FOR EXTERIOR
 DOORS. HOWEVER, THE PLANS DO NOT SPECIFY THAT THE DOORS
 ARE BEING REPLACED. PLEASE CLARIFY. PLEASE INDICATE ON
 THE DOOR PRODUCT APPROVAL THE SPECIFIC DOORS THAT WILL
 BE INSTALLED. DCA RULE 9N-3 AND CITY AMENDMENTS
 106.1.1) NOT ADDRESSED.
  
 4) (THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 SINGLE HUNG WINDOWS ARE PARTIALLY ILLEGIBLE AND ARE NOT
 LARGE MISSILE IMPACT RATED. PLEASE SUBMIT LEGIBLE
 PRODUCT APPROVALS. DCA RULE 9N-3.) THE NOA DRAWINGS ARE
 BEING CUT OFF WHEN PRINTED. IN ORDER FOR THE COMPLETE
 PRODUCT APPROVAL DRAWINGS TO PRINT YOU WILL NEED TO
 SHRINK THEM TO FIT ON THE 8-1/2 X 11 PAPER OR USE
 LARGER PAPER.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]