| 2012-01-20 16:36:42 | 2007 FBC W/2009 REVISIONS |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) (SHOW COMPLIANCE WITH FBC R317.1 FOR ONE HOUR FIRE |
| | RESISTANCE RATED FLOOR/CEILING ASSEMBLY SEPARATION |
| | BETWEEN THE TWO DWELLING UNITS. NOTE: HVAC DUCTWORK |
| | WILL REQUIRE DAMPERS IF PENETRATING THE FIRE RATED |
| | ASSEMBLY PER FBC R317.3.1.1.) A TENANT WALL SEPARATION |
| | DETAIL WAS PROVIDED ON SHEET T-1 OF THE REVISED PLANS. |
| | HOWEVER, THE TENANTS ARE SEPARATED BY A FLOOR CEILING |
| | ASSEMBLY. PROVIDE A LISTED ONE HOUR FIRE RATED |
| | FLOOR/CEILING ASSEMBLY DETAIL ON THE PLANS. INCLUDE THE |
| | LISTING NUMBER ON THE DETAIL. |
| | |
| | 2) (THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| | STRUCTURAL MULLIONS HAVE INCOMPLETE DRAWINGS. SUBMIT |
| | COMPLETE LEGIBLE DRAWINGS. DCA RULE 9N-3) THE NOA |
| | DRAWINGS ARE BEING CUT OFF WHEN PRINTED. IN ORDER FOR |
| | THE COMPLETE PRODUCT APPROVAL DRAWINGS TO PRINT YOU |
| | WILL NEED TO SHRINK THEM TO FIT ON THE 8-1/2 X 11 PAPER |
| | OR USE LARGER PAPER. |
| | |
| | 3) (PRODUCT APPROVALS WERE SUBMITTED FOR EXTERIOR |
| | DOORS. HOWEVER, THE PLANS DO NOT SPECIFY THAT THE DOORS |
| | ARE BEING REPLACED. PLEASE CLARIFY. PLEASE INDICATE ON |
| | THE DOOR PRODUCT APPROVAL THE SPECIFIC DOORS THAT WILL |
| | BE INSTALLED. DCA RULE 9N-3 AND CITY AMENDMENTS |
| | 106.1.1) NOT ADDRESSED. |
| | |
| | 4) (THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| | SINGLE HUNG WINDOWS ARE PARTIALLY ILLEGIBLE AND ARE NOT |
| | LARGE MISSILE IMPACT RATED. PLEASE SUBMIT LEGIBLE |
| | PRODUCT APPROVALS. DCA RULE 9N-3.) THE NOA DRAWINGS ARE |
| | BEING CUT OFF WHEN PRINTED. IN ORDER FOR THE COMPLETE |
| | PRODUCT APPROVAL DRAWINGS TO PRINT YOU WILL NEED TO |
| | SHRINK THEM TO FIT ON THE 8-1/2 X 11 PAPER OR USE |
| | LARGER PAPER. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |