Plan Review Notes
Plan Review Notes For Permit 11090198
Permit Number 11090198
Review Stop M
Sequence Number 1
Notes
Date Text
2011-10-05 16:50:012007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) THE MECHANICAL PLANS ARE REQUIRED TO HAVE THE NAME
 AND SIGNATURE OF THE QUALIFIER AND THE LICENSE NUMBER
 FOR THE MECHANICAL CONTRACTOR THAT IS DESIGNING THE
 PLANS UNDER THE DESIGN AND BUILD EXEMPTION OF
 FS471.003. NOTE: THIS CONTRACTOR WILL ALSO HAVE TO
 INSTALL THE SYSTEM. OTHERWISE, THE PLANS ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ENGINEER OR ARCHITECT
 THAT DESIGNED THE SYSTEM PER FS 471 AND 481.
  
 2) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY
 CALCULATION FORMS.
  
 3) THE ENERGY FORM SPECIFIES R-30 ATTIC INSULATION AND
 THE PLANS HAVE R-19. PLEASE CORRECT.
  
 4) THE 2007 FBC ENERGY CODE GLITCH AMENDMENTS SECTION
 N1104.AB.1.2 REQUIRES CEILINGS/FLOORS THAT ARE COMMON
 TO SEPARATE CONDITIONED TENANCIES TO BE INSULATED TO A
 MINIMUM OF R-11, SPACE PERMITTING.
  
 5) THE EXISTING SQUARE FOOTAGE OF LIVING SPACE
 SPECIFIED ON THE PLANS APPEARS TO BE LESS THAN
 INDICATED BY THE DIMENSIONS SHOWN ON THE DRAWINGS. THIS
 CAUSES THE TOTAL CONDITIONED SPACE ON THE PLANS TO BE
 LESS THAN SPECIFIED ON THE ENERGY FORMS. PLEASE
 CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]