| 2011-10-11 09:52:30 | 2007 FBC W/2009 REVISIONS |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE WINDOW AND DOOR PRESSURES SPECIFIED ON THE PLANS |
| | ARE INCORRECT FOR EXPOSURE CATEGORY C WITH A MEAN ROOF |
| | HEIGHT OF 19 FEET. PLEASE CORRECT. SEE FBC R301.2.1 |
| | |
| | 2) ON SHEET 2, THE WINDOW TYPES AND SIZES FOR THE |
| | SECOND FLOOR ADDITION ARE NOT SHOWN ON THE PLANS. |
| | PLEASE CORRECT. CITY AMENDMENTS 106.1.1 |
| | |
| | 3) THE AREA TABULATIONS FOR THE EXISTING STRUCTURE |
| | APPEAR TO BE INCORRECT BASED ON THE DIMENSIONS ON THE |
| | PLANS. PLEASE CORRECT. CITY AMENDMENTS 106.1.1 |
| | |
| | 4) ON PLAN SHEET 1, THE FRONT ELEVATION HAS A ROOF |
| | SLOPE OF 3/12 AND THE OTHER ELEVATIONS HAVE 4/12 |
| | SLOPES. PLEASE CLARIFY. CITY AMENDMENTS 106.1.1 |
| | |
| | 5) ON PLAN SHEET T-1, THE DESIGN PRESSURES FOR THE |
| | OPENINGS ARE INCORRECT FOR EXPOSURE CATEGORY C AND THE |
| | WRONG CODE EDITION AND EXPOSURE CATEGORY ARE SPECIFIED. |
| | FBC R301.2.1 PLEASE CORRECT. |
| | |
| | 6) SHOW COMPLIANCE WITH FBC R317.1 FOR ONE HOUR FIRE |
| | RESISTANCE RATED FLOOR/CEILING ASSEMBLY SEPARATION |
| | BETWEEN THE TWO DWELLING UNITS. NOTE: HVAC DUCTWORK |
| | WILL REQUIRE DAMPERS IF PENETRATING THE FIRE RATED |
| | ASSEMBLY PER FBC R317.3.1.1. |
| | |
| | 7) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| | STRUCTURAL MULLIONS HAVE INCOMPLETE DRAWINGS. SUBMIT |
| | COMPLETE LEGIBLE DRAWINGS. DCA RULE 9N-3 |
| | |
| | 8) PRODUCT APPROVALS WERE SUBMITTED FOR EXTERIOR DOORS. |
| | HOWEVER, THE PLANS DO NOT SPECIFY THAT THE DOORS ARE |
| | BEING REPLACED. PLEASE CLARIFY. PLEASE INDICATE ON THE |
| | DOOR PRODUCT APPROVAL THE SPECIFIC DOORS THAT WILL BE |
| | INSTALLED. DCA RULE 9N-3 AND CITY AMENDMENTS 106.1.1 |
| | |
| | 9) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| | SINGLE HUNG WINDOWS ARE PARTIALLY ILLEGIBLE AND ARE NOT |
| | LARGE MISSILE IMPACT RATED. PLEASE SUBMIT LEGIBLE |
| | PRODUCT APPROVALS. DCA RULE 9N-3. |
| | |
| | 10) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR STORM |
| | PANELS WITH AN INSTALLATION SCHEDULE AND A |
| | CORRESPONDING KEY PLAN. SEE FBC R301.2.1.2 AND DCA RULE |
| | 9N-3. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |