Plan Review Notes
Plan Review Notes For Permit 11090198
Permit Number 11090198
Review Stop B
Sequence Number 1
Notes
Date Text
2011-10-11 09:52:302007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE WINDOW AND DOOR PRESSURES SPECIFIED ON THE PLANS
 ARE INCORRECT FOR EXPOSURE CATEGORY C WITH A MEAN ROOF
 HEIGHT OF 19 FEET. PLEASE CORRECT. SEE FBC R301.2.1
  
 2) ON SHEET 2, THE WINDOW TYPES AND SIZES FOR THE
 SECOND FLOOR ADDITION ARE NOT SHOWN ON THE PLANS.
 PLEASE CORRECT. CITY AMENDMENTS 106.1.1
  
 3) THE AREA TABULATIONS FOR THE EXISTING STRUCTURE
 APPEAR TO BE INCORRECT BASED ON THE DIMENSIONS ON THE
 PLANS. PLEASE CORRECT. CITY AMENDMENTS 106.1.1
  
 4) ON PLAN SHEET 1, THE FRONT ELEVATION HAS A ROOF
 SLOPE OF 3/12 AND THE OTHER ELEVATIONS HAVE 4/12
 SLOPES. PLEASE CLARIFY. CITY AMENDMENTS 106.1.1
  
 5) ON PLAN SHEET T-1, THE DESIGN PRESSURES FOR THE
 OPENINGS ARE INCORRECT FOR EXPOSURE CATEGORY C AND THE
 WRONG CODE EDITION AND EXPOSURE CATEGORY ARE SPECIFIED.
 FBC R301.2.1 PLEASE CORRECT.
  
 6) SHOW COMPLIANCE WITH FBC R317.1 FOR ONE HOUR FIRE
 RESISTANCE RATED FLOOR/CEILING ASSEMBLY SEPARATION
 BETWEEN THE TWO DWELLING UNITS. NOTE: HVAC DUCTWORK
 WILL REQUIRE DAMPERS IF PENETRATING THE FIRE RATED
 ASSEMBLY PER FBC R317.3.1.1.
  
 7) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 STRUCTURAL MULLIONS HAVE INCOMPLETE DRAWINGS. SUBMIT
 COMPLETE LEGIBLE DRAWINGS. DCA RULE 9N-3
  
 8) PRODUCT APPROVALS WERE SUBMITTED FOR EXTERIOR DOORS.
 HOWEVER, THE PLANS DO NOT SPECIFY THAT THE DOORS ARE
 BEING REPLACED. PLEASE CLARIFY. PLEASE INDICATE ON THE
 DOOR PRODUCT APPROVAL THE SPECIFIC DOORS THAT WILL BE
 INSTALLED. DCA RULE 9N-3 AND CITY AMENDMENTS 106.1.1
  
 9) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 SINGLE HUNG WINDOWS ARE PARTIALLY ILLEGIBLE AND ARE NOT
 LARGE MISSILE IMPACT RATED. PLEASE SUBMIT LEGIBLE
 PRODUCT APPROVALS. DCA RULE 9N-3.
  
 10) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR STORM
 PANELS WITH AN INSTALLATION SCHEDULE AND A
 CORRESPONDING KEY PLAN. SEE FBC R301.2.1.2 AND DCA RULE
 9N-3.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]