| Plan Review Notes For Permit 11090174 |
| Permit Number |
11090174 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-09-12 11:38:14 | 11090174 | | | 1698 OLD OKEECHOBEE ROAD | | | 480 VOLT SERVICE | | | | | | PLEASE ADVISE HOW THIS INSTALLATION WILL COMPLY WITH | | | THE FOLLOWING CODE SECTIONS: | | | | | | A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED | | | BY ONLY ONE SERVICE. NEC 230.2 | | | EACH SERVICE DROP OR LATERAL SHALL SUPPLY ONLY ONE SET | | | OF SERVICE ENTRANCE CONDUCTORS. NEC 230.40 | | | VERIFY THERE ARE NOT MORE THAN SIX SETS OF DISCONNECTS | | | PER SERVICE GROUPED IN ANY ONE LOCATION. NEC 210.71 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|