 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE 1: CONTRACTOR SUBMITTED FIRE SPRINKLER AS-BUILT
 DRAWINGS OF THE FIRE SPRINKLER SYSTEM. A REVIEW OF
 THESE DRAWINGS INDICATES THE SPRINKLER SYSTEM DESIGN
 WITH ESFR SPRINKLERS (K=16.8) IS ADEQUATE FOR THE
 PROPOSED RACK STORAGE SYSTEM CONSISTING OF CLASS IV
 COMMODITIES STORED UP TO 25 FEET IN HEIGHT.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  