2011-09-08 11:15:391 NORTH CLEMATIS STREET
 PERMIT # 11090106
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 INDICATE ALL NEW OR EXISTING DOORS THAT ARE EQUIPPED
 WITH ELECTROMAGNETIC HARDWARE. INTERLOCK WITH THE
 SPRINKLER AND FIRE ALARM SYSTEM SHALL BE NOTED ON THE
 LIFE SAFETY PLANS, FIRE ALARM PLANS AND ACCESS CONTROL
 PLANS. ACCESS CONTROLLED EGRESS DOORS SHALL COMPLY WITH
 ALL EIGHT REQUIREMENTS LISTED IN SECTION 7.2.1.6.2 OF
 NFPA 101 FLORIDA EDITION 2007. INTERLOCK WITH THE
 SPRINKLER AND FIRE ALARM SYSTEM SHALL BE REFERENCED ON
 THE LIFE SAFETY PLANS AND ELECTRICAL FIRE ALARM SYSTEM
 DRAWINGS.
  
 SECTION 7.2.1.6.2 OF NFPA 101 FLORIDA EDITION 2007
 ALLOWS ACCESS CONTROLLED EGRESS DOORS PROVIDED THAT ALL
 EIGHT OF THE FOLLOWING CRITERIA ARE MET:
 1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO DETECT AN OCCUPANT APPROACHING DOORS THAT
 ARE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS UPON
 DETECTION OF AN APPROACHING OCCUPANT OR LOSS OF POWER
 TO THE SENSOR.
 2. LOSS OF POWER TO THE PART OF THE ACCESS CONTROL
 SYSTEM THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK
 THE DOORS IN THE DIRECTION OF EGRESS.
 3. THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 LOCATED VERTICALLY 40 TO 48 INCHES ABOVE THE FLOOR AND
 WITHIN 60 INCHES HORIZONTALLY OF THE SECURED DOORS.
 4. THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS
 PUSH TO EXIT.
 5. WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK,
 INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS,
 AND THE DOORS SHALL REMAIN UNLOCKED FOR NOT LESS THAN
 30 SECONDS.
 6. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
 7. MANUAL FIRE ALARM BOXES SHALL NOT BE REQUIRED TO
 UNLOCK THE DOORS.
 8. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER
 SYSTEM OR AUTOMATIC DETECTION SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
  
 DERRICK L. DANIELS, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6722
  
  
  