| Plan Review Notes For Permit 11090053 |
| Permit Number |
11090053 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-09-06 12:43:36 | 1800 SOUTH AUSTRALIAN AVENUE | | | PERMIT #11090053 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | *****EMERGENCY REPAIRS PERMIT***** | | | | | | BUILDING INITIATING DEVICES TO BE TESTED TO ENSURE NEW | | | FIRE ALARM PANEL CIRCUIT BOARD IS RECEIVING ALARM | | | SIGNALS. | | | | | | MAGNETIC DOOR LOCK RELEASE TO BE TIED INTO FIRE ALARM | | | SYSTEM. | | | | | | VERIFY FIRE PUMP IS MONITORED BY FIRE ALARM SYSTEM. | | | | | | FIRE ALARM CIRCUIT TO BE MARKED ON ELECTRICAL PANEL AND | | | ACCESS RESTRICTED TO CIRCUIT BREAKER. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | | | 2011-09-06 12:33:29 | OKAY TO ISSUE PER WJOLIN |
|