| Plan Review Notes For Permit 11090049 |
| Permit Number |
11090049 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-09-06 14:56:19 | 951 28TH ST. | | | 11090049 | | | ADD A 3 PHASE 240 VOLT ELECTRIC SERVICE | | | | | | PROVIDE DETAILS OR PICTURE OF ALL EXISTING SERVICES ON | | | THE BUILDING. NEC 215.15 | | | ALL SERVICE DISCONNECTS MUST BE GROUPED IN ONE | | | LOCATION. NEC 230.72 | | | VERIFY THE SERVICE EQUIPMENT IS CAPABLE TO INTERRUPT | | | THE AVAILABLE FAULT CURRENT. NEC 110.9 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|