| Plan Review Notes For Permit 11090032 |
| Permit Number |
11090032 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-09-27 09:48:26 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY MECHANICAL | | | | | | 1) SUBMIT TWO COPIES OF HEATING AND COOLING EQUIPMENT | | | SIZING CALCULATIONS. FBC R M1401.3 | | | | | | 2) SPECIFY THE SIZE OF ALL DUCTWORK, INCLUDING THE | | | FLEX, ON THE PLANS. | | | | | | 3) THE LICENSE NUMBER AND SIGNATURE OF THE QUALIFIER | | | FOR WHALEN AIR IS REQUIRED ON THE MECHANICAL PLANS. FS | | | 47.OO3 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|