Plan Review Notes
Plan Review Notes For Permit 11090032
Permit Number 11090032
Review Stop M
Sequence Number 1
Notes
Date Text
2011-09-27 09:48:262007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO COPIES OF HEATING AND COOLING EQUIPMENT
 SIZING CALCULATIONS. FBC R M1401.3
  
 2) SPECIFY THE SIZE OF ALL DUCTWORK, INCLUDING THE
 FLEX, ON THE PLANS.
  
 3) THE LICENSE NUMBER AND SIGNATURE OF THE QUALIFIER
 FOR WHALEN AIR IS REQUIRED ON THE MECHANICAL PLANS. FS
 47.OO3
  