Plan Review Notes
Plan Review Notes For Permit 11090032
Permit Number 11090032
Review Stop E
Sequence Number 1
Notes
Date Text
2011-09-29 17:47:2011090032
 255 CORDOVA RD
 ADDITION TO SFD
  
 PLEASE PROVIDE A PANEL SCHEDULE FOR EACH ELECTRIC
 PANEL. SHOW THE LOCATION OF EACH PANEL AND ELECTRIC
 METER ON THE PLAN. NEC 215.5
 INDICATE THE FEEDER AND CONDUIT SIZE FOR THE SUB PANEL.
 NEC 215.5
 ALL CIRCUITS IN THE GARAGE MUST ORIGINATE FROM A SUB
 PANEL LOCATED WITHIN THE GARAGE. NEC 250.32
 GROUNDING AND BONDING OF THE SUB PANEL IN THE GARAGE
 SHALL INCLUDE AN EQUIPMENT GROUNDING CONDUCTOR AND A
 GROUNDING ELECTRODE. NEC 250.32 (A) AND (B)
 EVERY ADDITION TO AN EXISTING BUILDING WITH A FIRE
 PLACE OR GAS FIRED APPLIANCES SHALL HAVE A CARBON
 MONOXIDE DETECTOR WITHIN 10 FEET OF EACH ROOM USED FOR
 SLEEPING PURPOSES. FBC R313.4
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  