| 2011-09-27 11:15:52 | 2007 FBC W/2009 REVISIONS |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE STRUCTURE IS LOCATED LESS THAN 600 FEET FROM THE |
| | INLAND WATERWAY. THEREFORE, IT IS EXPOSURE CATEGORY C. |
| | ACCORDING TO FBC R301.2.1.4.3, THE ROOF SHEATHING |
| | UPLIFT, AS WELL AS, THE ROOF TO WALL UPLIFT LOADS ARE |
| | REQUIRED TO BE INCREASED BY 20 PERCENT. CORRECTIONS TO |
| | THE EXPOSURE AND WIND LOADS ON SHEETS S-2 AND S-6 ARE |
| | REQUIRED |
| | |
| | 2) THE OPENING PRESSURES ON SHEET A-3, WHICH ARE BASED |
| | ON EXPOSURE B NEED TO BE INCREASED TO REFLECT EXPOSURE |
| | C. FBC R301.2.1 |
| | |
| | 3) PROVIDE DETAILS (SIZE/LOCATIONS) FOR THE ROOF |
| | SCUPPERS AND OVERFLOW SCUPPERS WITH CALCULATIONS. FBC |
| | R903.4 AND R903.4.1 SEE ALSO FBC P 1106 AND 1107 |
| | |
| | 4) SPECIFY THE SQUARE FEET OF LIVING AREA THAT IS BEING |
| | ADDED TO THE EXISTING STRUCTURE ON THE PLANS. CITY |
| | AMENDMENTS 106.1.2 |
| | |
| | 5) THE ROOF PLAN ON SHEET S-2 HAS CONFLICTING |
| | INFORMATION. BOTH 2 X 12 AND 2 X 8 RAFTERS ARE |
| | SPECIFIED AT THE VERANDA. PLEASE CORRECT. |
| | |
| | 6) SHOW COMPLIANCE WITH FBC R312 FOR THE VERANDA GUARD |
| | RAILS. |
| | |
| | 7) PROVIDE STRUCTURAL DETAILS FOR THE COVERED BREEZEWAY |
| | THAT ATTACHES THE RESIDENCE WITH THE GARAGE. FBC R |
| | 301.1 |
| | |
| | 8) SHOW COMPLIANCE WITH FBC R408 FOR CRAWL SPACE |
| | VENTILATION AND ACCESS. |
| | |
| | 9) SHOW COMPLIANCE WITH FBC R806 FOR ATTIC VENTILATION. |
| | |
| | 10) BOTH OF THE SECTION DRAWINGS ON SHEET S-2 ARE |
| | LABELED A-A. THE TOP ONE SHOULD BE LABELED B-B. PLEASE |
| | CORRECT. |
| | |
| | 11) THE TWO DRAWINGS ON THE TRUSS LAYOUT FROM THE TRUSS |
| | COMPANY NEED TO BE IDENTIFIED (LABELED). THERE DOES NOT |
| | APPEAR TO BE A ROOF LAYOUT OR ROOF TRUSS DRAWINGS FOR |
| | THE ADDITION. IT APPEARS THAT ONE OF THE DRAWINGS ON |
| | THE LAYOUT IS FOR FLOOR TRUSSES AND THE F01 TRUSS |
| | DRAWINGS APPEAR TO BE FLOOR TRUSSES BASED ON THE LOADS |
| | GIVEN. THE STRUCTURAL PLANS SPECIFY 2 X 12 JOISTS FOR |
| | BOTH FLOORS OF THE ADDITION. PLEASE CORRECT. |
| | |
| | 12) PLEASE MAKE THE FOLLOWING CORRECTIONS TO THE ENERGY |
| | CALCULATION FORMS. (1) THE ENERGY COMPLIANCE FORM IS |
| | REQUIRED TO BE SIGNED BY THE OWNER OR HIS AGENT. (2) |
| | SPECIFY THE INSULATION R-VALUE FOR THE THE ADDITION, |
| | WHICH IS A CRAWL SPACE NOT A SLAB ON GRADE. (3) THE |
| | PLANS SPECIFY R-19 ATTIC INSULATION AND THE ENERGY FORM |
| | LISTS R-30. (4) SPECIFY THE INSULATION FOR THE FLOOR |
| | BELOW THE VERANDA. (5) THE 2 X 8 EXTERIOR WOOD WERE NOT |
| | SHOWN ON THE FORM. (6) THE CEILING FANS ARE NOT |
| | SPECIFIED ON THE PLANS. IN ORDER TO RECEIVE THE CEILING |
| | FAN CREDIT, ONE 36" FAN IS REQUIRED IN THE BEDROOM AND |
| | TWO 48" FANS ARE REQUIRED IN THE LIVING ROOM. (6) |
| | CREDIT CAN NOT BE TAKEN FOR BOTH CEILING FANS AND CROSS |
| | VENTILATION PER 2007 ENERGY GLITCH AMENDMENTS C4.2.1.1. |
| | |
| | 13) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY |
| | AMENDMENTS 106.3.3 |
| | |
| | 14) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED |
| | TO INSTALL THE ROOF TILES. IF AN ADHESIVE WILL BE USED |
| | SUBMIT THE PRODUCT APPROVALS FOR IT. FBC R905.3.7 AND |
| | DCA RULE 9N-3 |
| | |
| | 15) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE |
| | STRUCTURAL WINDOW MULLIONS. DCA RULE 9N-3 |
| | |
| | 16) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE |
| | SINGLE HUNG BATHROOM WINDOW . DCA RULE 9N-3 |
| | |
| | 17) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE |
| | ROOFING MATERIALS THAT WILL BE USED ON THE FLAT ROOF. |
| | PROVIDE RAS 117 CALCULATIONS FOR ENHANCED FASTENING. |
| | DCA RULE 9N-3 |
| | |