2011-09-27 11:15:522007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED LESS THAN 600 FEET FROM THE
 INLAND WATERWAY. THEREFORE, IT IS EXPOSURE CATEGORY C.
 ACCORDING TO FBC R301.2.1.4.3, THE ROOF SHEATHING
 UPLIFT, AS WELL AS, THE ROOF TO WALL UPLIFT LOADS ARE
 REQUIRED TO BE INCREASED BY 20 PERCENT. CORRECTIONS TO
 THE EXPOSURE AND WIND LOADS ON SHEETS S-2 AND S-6 ARE
 REQUIRED
  
 2) THE OPENING PRESSURES ON SHEET A-3, WHICH ARE BASED
 ON EXPOSURE B NEED TO BE INCREASED TO REFLECT EXPOSURE
 C. FBC R301.2.1
  
 3) PROVIDE DETAILS (SIZE/LOCATIONS) FOR THE ROOF
 SCUPPERS AND OVERFLOW SCUPPERS WITH CALCULATIONS. FBC
 R903.4 AND R903.4.1 SEE ALSO FBC P 1106 AND 1107
  
 4) SPECIFY THE SQUARE FEET OF LIVING AREA THAT IS BEING
 ADDED TO THE EXISTING STRUCTURE ON THE PLANS. CITY
 AMENDMENTS 106.1.2
  
 5) THE ROOF PLAN ON SHEET S-2 HAS CONFLICTING
 INFORMATION. BOTH 2 X 12 AND 2 X 8 RAFTERS ARE
 SPECIFIED AT THE VERANDA. PLEASE CORRECT.
  
 6) SHOW COMPLIANCE WITH FBC R312 FOR THE VERANDA GUARD
 RAILS.
  
 7) PROVIDE STRUCTURAL DETAILS FOR THE COVERED BREEZEWAY
 THAT ATTACHES THE RESIDENCE WITH THE GARAGE. FBC R
 301.1
  
 8) SHOW COMPLIANCE WITH FBC R408 FOR CRAWL SPACE
 VENTILATION AND ACCESS.
  
 9) SHOW COMPLIANCE WITH FBC R806 FOR ATTIC VENTILATION.
  
 10) BOTH OF THE SECTION DRAWINGS ON SHEET S-2 ARE
 LABELED A-A. THE TOP ONE SHOULD BE LABELED B-B. PLEASE
 CORRECT.
  
 11) THE TWO DRAWINGS ON THE TRUSS LAYOUT FROM THE TRUSS
 COMPANY NEED TO BE IDENTIFIED (LABELED). THERE DOES NOT
 APPEAR TO BE A ROOF LAYOUT OR ROOF TRUSS DRAWINGS FOR
 THE ADDITION. IT APPEARS THAT ONE OF THE DRAWINGS ON
 THE LAYOUT IS FOR FLOOR TRUSSES AND THE F01 TRUSS
 DRAWINGS APPEAR TO BE FLOOR TRUSSES BASED ON THE LOADS
 GIVEN. THE STRUCTURAL PLANS SPECIFY 2 X 12 JOISTS FOR
 BOTH FLOORS OF THE ADDITION. PLEASE CORRECT.
  
 12) PLEASE MAKE THE FOLLOWING CORRECTIONS TO THE ENERGY
 CALCULATION FORMS. (1) THE ENERGY COMPLIANCE FORM IS
 REQUIRED TO BE SIGNED BY THE OWNER OR HIS AGENT. (2)
 SPECIFY THE INSULATION R-VALUE FOR THE THE ADDITION,
 WHICH IS A CRAWL SPACE NOT A SLAB ON GRADE. (3) THE
 PLANS SPECIFY R-19 ATTIC INSULATION AND THE ENERGY FORM
 LISTS R-30. (4) SPECIFY THE INSULATION FOR THE FLOOR
 BELOW THE VERANDA. (5) THE 2 X 8 EXTERIOR WOOD WERE NOT
 SHOWN ON THE FORM. (6) THE CEILING FANS ARE NOT
 SPECIFIED ON THE PLANS. IN ORDER TO RECEIVE THE CEILING
 FAN CREDIT, ONE 36" FAN IS REQUIRED IN THE BEDROOM AND
 TWO 48" FANS ARE REQUIRED IN THE LIVING ROOM. (6)
 CREDIT CAN NOT BE TAKEN FOR BOTH CEILING FANS AND CROSS
 VENTILATION PER 2007 ENERGY GLITCH AMENDMENTS C4.2.1.1.
  
 13) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 106.3.3
  
 14) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED
 TO INSTALL THE ROOF TILES. IF AN ADHESIVE WILL BE USED
 SUBMIT THE PRODUCT APPROVALS FOR IT. FBC R905.3.7 AND
 DCA RULE 9N-3
  
 15) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 STRUCTURAL WINDOW MULLIONS. DCA RULE 9N-3
  
 16) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 SINGLE HUNG BATHROOM WINDOW . DCA RULE 9N-3
  
 17) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 ROOFING MATERIALS THAT WILL BE USED ON THE FLAT ROOF.
 PROVIDE RAS 117 CALCULATIONS FOR ENHANCED FASTENING.
 DCA RULE 9N-3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW