| Plan Review Notes For Permit 11090023 |
| Permit Number |
11090023 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-09-09 16:18:35 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | COMMENTS FROM PREVIOUS LIST: | | | | | | 1. ADDRESSED | | | | | | 2. ENHANCED FASTENING FOR THE FLAT DECKS REQUIRE | | | CALCULATIONS BY AN ARCHITECT, ENGINEER, OR REGISTERED | | | ROOF CONSULTANT, SEE GENERAL LIMITATION #7, LAST PAGE | | | OF PRODUCT APPROVAL. | | | | | | 2ND REVIEW, THE DESIGN PRESSURES SPECIFIED BY ARCHITECT | | | COLETTE SATCHELL ARE TOO LOW. SEE FBC RAS 127, FBC | | | RESIDENTIAL TABLE 301.2(2) AND (3). THIS STRUCTURE IS | | | LOCATED IN 140MPH EXPOSURE C, PRESSURES OF -47.66, | | | -55.01, -73.6 ARE TOO LOW. SEE ALSO ASCE7-05, SECTION | | | 6.2, DEFINITION OF "EFFEECTIVE WIND AREA", FOR CLADDING | | | FASTENERS, THE EFFECTIVE WIND AREA SHALL NOT BE GREATER | | | THAN THE AREA THAT IS TRIBUTARY TO AN INDIVIDUAL | | | FASTENER. THEREFORE, AREA IS < 10' FOR ALL ZONES. | | | PLEASE FEEL FREE TO CONTACT ME TO DISCUSS. | | | | | | NEW COMMENT: | | | | | | 3. THE NEW SHINGLE PRODUCT APPROVALS ARE TO BE REVIEWED | | | BY HISTORIC PRIOR TO RESUBMITTAL. | | | | | | | | | |
|