2011-09-09 16:18:35****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. ADDRESSED
  
 2. ENHANCED FASTENING FOR THE FLAT DECKS REQUIRE
 CALCULATIONS BY AN ARCHITECT, ENGINEER, OR REGISTERED
 ROOF CONSULTANT, SEE GENERAL LIMITATION #7, LAST PAGE
 OF PRODUCT APPROVAL.
  
 2ND REVIEW, THE DESIGN PRESSURES SPECIFIED BY ARCHITECT
 COLETTE SATCHELL ARE TOO LOW. SEE FBC RAS 127, FBC
 RESIDENTIAL TABLE 301.2(2) AND (3). THIS STRUCTURE IS
 LOCATED IN 140MPH EXPOSURE C, PRESSURES OF -47.66,
 -55.01, -73.6 ARE TOO LOW. SEE ALSO ASCE7-05, SECTION
 6.2, DEFINITION OF "EFFEECTIVE WIND AREA", FOR CLADDING
 FASTENERS, THE EFFECTIVE WIND AREA SHALL NOT BE GREATER
 THAN THE AREA THAT IS TRIBUTARY TO AN INDIVIDUAL
 FASTENER. THEREFORE, AREA IS < 10' FOR ALL ZONES.
 PLEASE FEEL FREE TO CONTACT ME TO DISCUSS.
  
 NEW COMMENT:
  
 3. THE NEW SHINGLE PRODUCT APPROVALS ARE TO BE REVIEWED
 BY HISTORIC PRIOR TO RESUBMITTAL.
  
  
  