| 2011-09-09 09:49:26 | FBC 2007 PLUMBING REVIEW #1. | | | DENIED: | | | | | | 1. KITCHEN SINK - HOT WATER REQUIRED 607.1 WHERE | | | REQUIRED. IN OCCUPIED STRUCTURES, HOT WATER SHALL BE | | | SUPPLIED TO ALL PLUMBING FIXTURES AND EQUIPMENT | | | UTILIZED FOR BATHING, WASHING, CULINARY PURPOSES, | | | CLEANSING, LAUNDRY OR BUILDING MAINTENANCE. | | | | | | 2. SANITARY FOR KITCHEN SINK IS SHOWN CONNECTING TO THE | | | RESTROOM WET VENT SYSTEM - SHALL BE CONNECTED | | | DOWNSTREAM OF WET VENT. | | | 909.1 HORIZONTAL WET VENT PERMITTED. ANY COMBINATION OF | | | FIXTURES WITHIN TWO BATHROOM GROUPS LOCATED ON THE SAME | | | FLOOR LEVEL IS PERMITTED TO BE VENTED BY A HORIZONTAL | | | WET VENT. THE WET VENT SHALL BE CONSIDERED THE VENT FOR | | | THE FIXTURES AND SHALL EXTEND FROM THE CONNECTION OF | | | THE DRY VENT ALONG THE DIRECTION OF THE FLOW IN THE | | | DRAIN PIPE TO THE MOST DOWNSTREAM FIXTURE DRAIN | | | CONNECTION TO THE HORIZONTAL BRANCH DRAIN. ONLY THE | | | FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO | | | THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL | | | FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL | | | WET VENT. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|