Plan Review Notes
Plan Review Notes For Permit 11080860
Permit Number 11080860
Review Stop P
Sequence Number 1
Notes
Date Text
2011-09-09 09:49:26FBC 2007 PLUMBING REVIEW #1.
 DENIED:
  
 1. KITCHEN SINK - HOT WATER REQUIRED 607.1 WHERE
 REQUIRED. IN OCCUPIED STRUCTURES, HOT WATER SHALL BE
 SUPPLIED TO ALL PLUMBING FIXTURES AND EQUIPMENT
 UTILIZED FOR BATHING, WASHING, CULINARY PURPOSES,
 CLEANSING, LAUNDRY OR BUILDING MAINTENANCE.
  
 2. SANITARY FOR KITCHEN SINK IS SHOWN CONNECTING TO THE
 RESTROOM WET VENT SYSTEM - SHALL BE CONNECTED
 DOWNSTREAM OF WET VENT.
 909.1 HORIZONTAL WET VENT PERMITTED. ANY COMBINATION OF
 FIXTURES WITHIN TWO BATHROOM GROUPS LOCATED ON THE SAME
 FLOOR LEVEL IS PERMITTED TO BE VENTED BY A HORIZONTAL
 WET VENT. THE WET VENT SHALL BE CONSIDERED THE VENT FOR
 THE FIXTURES AND SHALL EXTEND FROM THE CONNECTION OF
 THE DRY VENT ALONG THE DIRECTION OF THE FLOW IN THE
 DRAIN PIPE TO THE MOST DOWNSTREAM FIXTURE DRAIN
 CONNECTION TO THE HORIZONTAL BRANCH DRAIN. ONLY THE
 FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO
 THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET VENT.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  