| 2011-09-13 14:35:06 | BUILDING PLAN REVIEW |
| | PERMIT: 11080860 |
| | ADD: 2100 45TH ST # A-2A |
| | CONT: COVENANT CONSTRUCTION |
| | TEL: (561)255-1855 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-000 CODE CLASSIFICATION INDICATES THIS |
| | BUILDING TO BE A TYPE T UNPROTECTED/ NON-SPINKLERED. |
| | PLEASE REVIEW TABLE 601 FOR TYPE I CONSTRUCTION THERE |
| | IS EITHER A TYPE I-A OR TYPE TYPE I-B BOTH OF WHICH |
| | HAVE FIRE RATING ON THEIR STRUCTURAL MEMBERS, PLEASE |
| | REVIEW FIRE RATING IN HOURS OF STRUCTURAL COMPONENTS |
| | AND MEMBERS. |
| | |
| | 2) PLEASE REVIEW DOOR 4, 5 7 & 9 AND THIER REQUIRED |
| | CLEAR WIDTH, SHEET A-500 DOOR SCHEDULE INDICATE THESE |
| | DOORS TO BE A 2'-8" DOOR. PLEASE REVIEW 2007/ 09 FBC-B |
| | 1008.1.1 AND REQUIRED CLEAR WIDTH. THE MINIMUM WIDTH OF |
| | EACH DOOR OPENING SHALL BE SUFFICIENT FOR THE OCCUPANT |
| | LOAD THEREOF AND SHALL PROVIDE A CLEAR WIDTH OF NOT |
| | LESS THAN 32 INCHES (813 MM). CLEAR OPENINGS OF |
| | DOORWAYS WITH SWINGING DOORS SHALL BE MEASURED BETWEEN |
| | THE FACE OF THE DOOR AND THE STOP, WITH THE DOOR OPEN |
| | 90 DEGREES (1.57 RAD). WHERE THIS SECTION REQUIRES A |
| | MINIMUM CLEAR WIDTH OF 32 INCHES (813 MM) AND A DOOR |
| | OPENING INCLUDES TWO DOOR LEAVES WITHOUT A MULLION, ONE |
| | LEAF SHALL PROVIDE A CLEAR OPENING WIDTH OF 32 INCHES |
| | (813 MM). |
| | |
| | 3) DOOR # 16 SWINGS INTO THE CLEAR FLOOR SPACE OF THE |
| | DRINKING FOUNTAIN. 11-4.15.5 CLEARANCES. |
| | |
| | (1) A-100 WALL- AND POST-MOUNTED CANTILEVERED UNITS |
| | SHALL HAVE A CLEAR KNEE SPACE BETWEEN THE BOTTOM OF THE |
| | APRON AND THE FLOOR OR GROUND AT LEAST 27 INCHES (685 |
| | MM) HIGH, 30 INCHES (760 MM) WIDE, AND 17 INCHES TO 19 |
| | INCHES (430 MM TO 485 MM) DEEP [SEE FIGURE 27(A) AND |
| | FIGURE 27(B)]. SUCH UNITS SHALL ALSO HAVE A MINIMUM |
| | CLEAR FLOOR SPACE 30 INCHES BY 48 INCHES (760 MM BY |
| | 1219 MM) TO ALLOW A PERSON IN A WHEELCHAIR TO APPROACH |
| | THE UNIT FACING FORWARD. |
| | |
| | 4) A-100 PLEASE SEE DOORS 19 & 20 FOR THEIR MANEUVERING |
| | CLEARENCES AT DOORS. 11-4.13.6 MANEUVERING CLEARANCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS THAT |
| | ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN |
| | IN FIGURE 25. THE FLOOR OR GROUND AREA WITHIN THE |
| | REQUIRED CLEARANCES SHALL BE LEVEL AND CLEAR. |
| | |
| | 5) ADDITIONAL INFORMATION REQUIRED, 106.1.2 PLANS |
| | INDICATE TWO LABORATORIES, PLEASE PROVIDE WHAT TYPE OF |
| | ACTIVITIES WILL TAKE PLACE IN THESE ROOMS, WILL EXTRA |
| | VENTILATION BE REQUIRED, EXHAUST HOODS? MEDIGAL GAS? |
| | HOT WATER? |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |