2011-08-30 09:57:28RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AS
 REQUIRED BY GENERAL LIMITATION #7 TO MEET THE DESIGN
 PRESSURES REQUIRED BY SEC. R301.2.1.4.3.
  
 2- NOA 07-0730.03 SUBMITTED WAS SUPERSEDED BY
 MIAMI-DADE. NEED TO PROVIDE CURRENT NOA (2 COPIES).
  
 3- CLARIFY WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED. THERE ARE TWO DIFFERENT ASSEMBLIES
 SUBMITTED. ASSEMBLY ON PAGES 6 AND 7 IS FOR AN
 INSULATED ASSEMBLY. AND, ASSEMBLY ON PAGE 17 IS FOR A
 NON-INSULATED ASSEMBLY.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER