2011-09-06 09:39:41801 SOUTH OLIVE AVENUE - UNIT #806/#807
 PERMIT #11080775
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO*****
  
 SMOKE ALARMS SHALL ALL BE TIED TOGETHER SO THAT WHEN
 ONE SMOKE ALARM SOUNDS, ALL SMOKE ALARMS IN THE UNIT
 SOUND TOGETHER.
  
 NO FIRE SPRINKLER SCOPE INDICATED ON PLANS. SEPARATE
 PLANS AND PERMIT REQUIRED FOR THE MODIFICATION OF THE
 FIRE SPRINKLER SYSTEM.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  