| Notes |
| Date |
Text |
| 2012-02-01 19:00:45 | BUILDING PLAN REVIEW | | | *****REVISION REQ"D***** | | | ROBERT BROWN (561) 805 6652 | | | E-MAIL: [email protected] | | | | | | REVIEW OF SITE SPECIFIC PRODUCT APPROVAL APPLICATION: | | | | | | | | | REVISION REQUIRED: | | | **************************** | | | PER THE PREVIOUS DISCUSSIONS WITH BIJAN ABIDIAN AN | | | ADDITIONAL CALCULATION TO JUSTIFY THE 2"X2" HORIZONTAL | | | MULLION BETWEEN THE TRANSOM AND THE DOOR MUST BE | | | SUBMITTED, REVIEWED AND STAMPED PRIOR TO INSPECTION. | | | THE CALCLATION CAN BE A SIMPLY SUPPORTED BEAM ANALYSIS | | | BASED ON THE WIND LOADS ON THE DOOR AND THE TRANSOM, OR | | | IT CAN BE A RATIONAL ANALYSIS COMPARING THE PROPOSED | | | MULLION TO ONE THAT HAS BEEN TESTED AND HAS A PRODUCT | | | APPROVAL. | | | | | | THE ADDITIONAL CALCULATIONS MUST BE SUBMITTED AS A | | | REVISION AND A REVIEW FEE OF $50 WILL BE ASSESSED. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | TELEPHONE: (561) 805 6652 ROBERT BROWN | | | E-MAIL: [email protected] |
|