| Plan Review Notes For Permit 11080749 |
| Permit Number |
11080749 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2011-12-28 13:40:06 | AFTER A QUICK REVIEW OF THE EMAILED DOCUMENTS AND | | | PREVIOUSLY SUBMITTED DRAWINGS, I HAVE SOME CONCERNS. | | | THE PREVIOUS DRAWINGS INDICATE A DOUBLE OUT-SWING DOOR | | | ASSEMBLY WITH SIDE LITES AND AN ARCHED FIXED GLASS | | | TRANSOM. THE ANALYSIS DOES NOT ADDRESS THE TRANSOM NOR | | | THE STRUCTURAL MULLION BETWEEN THE IT AND THE | | | DOORS/SITE LITES. THERE ARE ALSO SOME DISCREPANCIES | | | BETWEEN THE DRAWINGS FROM GOULDY AND THE ANALYSIS FROM | | | THE NEW ENGINEER. THE DRAWINGS SPECIFY 1/8" THICK | | | ALUMINUM FOR THE CUSTOM DOORS AND THE ANALYSIS HAS 1/4" | | | ALUMINUM. THE TESTED DOOR PRODUCT APPROVAL HAS 2 LAYERS | | | OF 3/16" TEMPERED GLASS WITH A .090 PVB INTERIOR LAYER | | | AND THE ANALYSIS HAS 3/16" TEMPERED GLASS. THE THERE | | | ARE TWO OPTIONS FOR THE LOCKING HARDWARE FOR THE TESTED | | | DOOR. OPTION ONE HAS A DEAD BOLT, A CONVENTIONAL LOCK | | | SET AND FLUSH BOLTS. BOTH OPTIONS HAVE TWO FLUSH BOLTS | | | ON EACH DOOR. THE ANALYSIS SPECIFIES BALDWIN VERSAILLES | | | LOCKING HARDWARE AND DOES NOT ELABORATE. THE DRAWING | | | DOES NOT SHOW ANY LOCKING HARDWARE. THE NOA NUMBER | | | SPECIFIED ON THE ANALYSIS (06-0327.03) DOES NOT MATCH | | | THE ONE IN THE EMAIL PDF (06-0327.02). |
|