| Plan Review Notes For Permit 11080749 |
| Permit Number |
11080749 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2011-12-20 15:00:17 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN (561) 805 6652 | | | E-MAIL: [email protected] | | | | | | | | | REVIEW OF "ENTRY DOOR STRUCTURAL CALCULATIONS, DECEMBER | | | 2011" PREPARED BY REZA JAVIDAN, P.E. | | | | | | PLEASE SEE PREVIOUS PLAN REVIEW DATED 12/2/11. IN ORDER | | | TO ISSUE A SITE SPECIFIC PRODUCT APPROVAL WE MUST START | | | WITH A FLORIDA STATE OR MIAMI-DADE PRODUCT APPROVAL FOR | | | A DOOR PRODUCT THAT HAS BEEN TESTED. THE RATIONAL | | | ANALYSIS SHOULD COMPARE THE PROPOSED DOOR TO THE DOOR | | | THAT WAS TESTED FOR THE PRODUCT APPROVAL AND SHOW THAT | | | THE PROPOSED DOOR IS EQUAL TO OR BETTER THAN THE TESTED | | | DOOR WITH RESPECT TO GLASS TYPE/THICKNESS, SAME OR | | | SMALLER GLASS PANEL SIZE, STILE AND RAIL STRENGTH, | | | HARDWARE STRENGTH, FRAME STRENGTH, FRAME ANCHORAGE, | | | ETC. | | | | | | THE SUBMITTED "ENTRY DOOR STRUCTURAL CALCULATIONS, | | | DECEMBER 2011" PREPARED BY REZA JAVIDAN, P.E. DO NOT | | | MEET THE ABOVE REQUIREMENTS FOR A SITE SPECIFIC PRODUCT | | | APPROVAL. | | | | | | END OF REVIEW COMMENTS | | | TELEPHONE: (561) 805 6652 ROBERT BROWN | | | E-MAIL: [email protected] |
|