Plan Review Notes
Plan Review Notes For Permit 11080749
Permit Number 11080749
Review Stop B
Sequence Number 1
Notes
Date Text
2011-08-31 14:42:342007 FBC W/2009 REVISIONS
  
 REVISION DENIED BY BUILDING
  
 THE PROPOSED COMPONENT CONSISTS OF A PAIR OF OUTSWING
 DOORS WITH SIDELITES AND A FIXED TRANSOM WINDOW ABOVE.
  
 1 ) PRODUCT APPROVAL. RULE 9N-3 FAC (FORMALLY RULE
 9B-72)
 FOR PRODUCTS WHICH DO NOT HAVE STATEWIDE
 PRODUCT APPROVAL, LOCAL PRODUCT APPROVAL
 CAN BE ACHIEVED IF THERE IS A QUALITY
 ASSURANCE PROGRAM IN PLACE WITH A STATE
 APPROVED QUALITY ASSURANCE ENTITY. IF
 NEITHER IS APPLICABLE, THEN SITE
 SPECIFIC APPROVAL CAN BE ISSUED FOR
 'CUSTOM PRODUCTS' ONLY. LOCAL PRODUCT
 APPROVAL WILL ALLOW A PRODUCT TO BE
 USED, IN ACCORDANCE WITH THE TEST
 CRITERIA, THROUGHOUT THE JURISDICTION OF
 WEST PALM BEACH. SITE SPECIFIC PRODUCT
 APPROVAL WILL ALLOW A PRODUCT TO BE
 USED ONLY ON THE PROJECT FOR WHICH THAT
 SITE SPECIFIC APPROVAL IS GRANTED.
 LOCAL AND SITE SPECIFIC PRODUCT APPROVAL
 APPLICATION FORMS ARE AVAILABLE FROM
 THIS OFFICE OR ON THE CONSTRUCTION SERVICES WEBSITE
 HTTP://WWW.WPB.ORG/CONSTRUCTION/PERMITS_FORMS.PHP
 APPROVED QUALITY ASSURANCE
 ENTITIES ARE LISTED ON THE DCA WEBSITE:
 FLORIDABUILDING.ORG/PR/PR_ORG_SRCH.ASPX
 (IF YOU FIND THAT THE QUOTED WEB PAGE IS
 NO LONGER AVAILABLE, PLEASE INFORM THE
 PLAN REVIEWER)
  
 2) SITE SPECIFIC PRODUCT APPROVAL CHECK LIST
  
 CODE REFERENCES:
 FBC R613.4.3 CUSTOM (ONE OF A KIND) DOORS
 FBC R613.4.4 DOOR COMPONENTS
 FBC R613.6 ANCHORAGE METHODS
 FBC 104.11 ALTERNATE MATERIALS AND METHODS
  
  
 INFORMATION REQUIRED
  
  
 1- A COMPLETED CITY OF WEST PALM BEACH SITE SPECIFIC
 PRODUCT APPROVAL FORM.
 2- A SIGNED AND SEALED REPORT FROM A STATE OF FLORIDA
 APPROVED TESTING LABORATORY.
 3- SIGNED AND SEALED ENGINEERING (CALCULATIONS AND
 DRAWINGS) FROM A FLORIDA LICENSED ENGINEER OR ARCHITECT
 EXPERIENCED IN THIS WORK. NOTE: CALCULATIONS MUST
 ADDRESS CONSTRUCTION AND INSTALLATION OF THE PRODUCT
 AND ALL COMPONENTS. DESIGN WIND-LOAD PRESSURES MUST BE
 SPECIFIED. ALL LIMITATIONS MUST BE LISTED.
 4- PRIOR TO RECEIVING A CERTIFICATE OF OCCUPANCY FOR
 THE JOB, A SIGNED AND SEALED LETTER FROM THE ENGINEER
 OR ARCHITECT MUST BE SUBMITTED CERTIFYING THAT THE
 PRODUCT WAS CONSTRUCTED AND INSTALLED ACCORDING TO THE
 DESIGN SPECIFICATIONS THAT WERE SUBMITTED.
  
 3) FBC R301.2.1.2 REQUIRES GLAZED OPENING PROTECTION TO
 MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST AND TO
 BE TESTED AT 1.5 TIMES THE DESIGN PRESSURE.
  
 4) SHOW COMPLIANCE WITH FBC R311.4.4 WHICH REQUIRES
 EGRESS DOORS TO BE READILY OPENABLE WITHOUT THE USE OF
 KEY OR SPECIAL KNOWLEDGE OR EFFORT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW