 PERMIT #11080740
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO ADDRESS PROVIDED ON DRAWINGS.
  
 PROVIDE MATERIAL SAFETY DATA SHEETS (MSDS) FOR 19%
 AMMONIA HYDROXIDE.
  
 INDICATE IF THE BUILDING IS PROTECTED BY AN AUTOMATIC
 FIRE SPRINKLER SYSTEM.
  
 CONFIRM THE TOTAL QUANTITY OF AMMONIA HYDROXIDE TO BE
 LOCATED IN THE ROOM IS 320 GALLONS (TANK #1 - 155
 GALLONS, TANK #2 - 55 GALLONS, SPARE TANK - 55 GALLONS
 (X2)).
  
 VERIFY AMMONIA HYDROXIDE ROOM IS SEPARATED FROM
 ADJACENT CHLORINE ROOM WITH A FIRE RESISTANCE RATING OF
 AT LEAST ONE-HOUR.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  