| 2011-08-31 14:54:08 | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | KITCHENETTE: IF THE KITCHENETTE IS ACTUALLY USED AS A |
| | BREAK ROOM THEN COMPLIANCE WITH 2007/ 09 FBC-B 11-4.24 |
| | IS REQUIRED. |
| | 11-4.24 SINKS. |
| | 11-4.24.1 GENERAL. SINKS REQUIRED TO BE ACCESSIBLE BY |
| | SECTION 11-4.1 SHALL COMPLY WITH SECTION 11-4.24. |
| | 11-4.24.2 HEIGHT. SINKS SHALL BE MOUNTED WITH THE |
| | COUNTER OR RIM NO HIGHER THAN 34 INCHES (865 MM) ABOVE |
| | THE FINISH FLOOR. |
| | 11-4.24.3 KNEE CLEARANCE. KNEE CLEARANCE THAT IS AT |
| | LEAST 27 INCHES (685 MM) HIGH, 30 INCHES (760 MM) WIDE, |
| | AND 19 INCHES (485 MM) DEEP SHALL BE PROVIDED |
| | UNDERNEATH SINKS. |
| | 11-4.24.4 DEPTH. EACH SINK SHALL BE A MAXIMUM OF 61/2 |
| | INCHES (165 MM) DEEP. |
| | 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT |
| | LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) |
| | COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN |
| | FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR |
| | FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL |
| | EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE |
| | SINK (SEE FIGURE 32). |
| | 11-4.24.6 EXPOSED PIPES AND SURFACES. HOT WATER AND |
| | DRAIN PIPES EXPOSED UNDER SINKS SHALL BE INSULATED OR |
| | OTHERWISE CONFIGURED SO AS TO PROTECT AGAINST CONTACT. |
| | THERE SHALL BE NO SHARP OR ABRASIVE SURFACES UNDER |
| | SINKS. |
| | 11-4.24.7 FAUCETS. FAUCETS SHALL COMPLY WITH SECTION |
| | 11-4.27.4. LEVER-OPERATED, PUSH-TYPE, TOUCH-TYPE, OR |
| | ELECTRONICALLY CONTROLLED MECHANISMS ARE ACCEPTABLE |
| | DESIGNS. |
| | |