| Plan Review Notes For Permit 11080680 |
| Permit Number |
11080680 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-11-03 11:42:28 | 11080680 | | | 509 27TH ST. | | | INTERIOR RENOVATION | | | | | | THE ELECTRICAL PLAN NEEDS TO BE SIGNED BY THE DESIGN | | | PROFESSIONAL . THE PLAN SHOULD DELINEATE THE SCOPE OF | | | WORK BETWEEN NEW AND EXISTING. SHOW AC AND HEATING. | | | CLEARLY SHOW THE INTERCONNECTED SMOKE ALARMS AND CARBON | | | MONOXIDE ALARMS AS REQUIRED BOTH WITHIN AND OUTSIDE THE | | | SLEEPING AREAS. FBC R313 | | | ALL NEW BRANCH CIRCUITS MUST BE PROTECTED WITH ARC | | | FAULT CIRCUIT INTERRUPTERS. NEC 210.12 | | | KITCHEN COUNTER TOP AND BATHROOM RECEPTACLES MUST BE | | | GFCI PROTECTED. NEC 210.8 | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT NEC 406.11 | | | BATHROOMS REQUIRE DEDICATED 20 AMP BRANCH CIRCUITS. NEC | | | 210-11(C)(3) | | | A BONDING STRIP IS REQUIRED AT SERVICE GROUND NEC | | | 250.94 | | | GFCI PROTECTED RECEPTACLES ARE REQUIRED AT FRONT AND | | | REAR ELEVATIONS. NEC 210.8 | | | AN ELECTRICAL RISER WITH PANEL SCHEDULE AND LOAD | | | CALCULATION IS REQUIRED IF THE HOME IS BEING REWIRED. | | | SHOW SERVICE AND PANEL BOARD LOCATIONS. NEC 215.15 | | | IF THE SCOPE OF RECONSTRUCTION INCLUDES AN ELECTRICAL | | | CONNECTION TO THE GARAGE FROM THE HOUSE THAN A SPECIFIC | | | WIRING METHOD IS REQUIRED. NEC 250.32 | | | | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|