2011-11-03 11:42:2811080680
 509 27TH ST.
 INTERIOR RENOVATION
  
 THE ELECTRICAL PLAN NEEDS TO BE SIGNED BY THE DESIGN
 PROFESSIONAL . THE PLAN SHOULD DELINEATE THE SCOPE OF
 WORK BETWEEN NEW AND EXISTING. SHOW AC AND HEATING.
 CLEARLY SHOW THE INTERCONNECTED SMOKE ALARMS AND CARBON
 MONOXIDE ALARMS AS REQUIRED BOTH WITHIN AND OUTSIDE THE
 SLEEPING AREAS. FBC R313
 ALL NEW BRANCH CIRCUITS MUST BE PROTECTED WITH ARC
 FAULT CIRCUIT INTERRUPTERS. NEC 210.12
 KITCHEN COUNTER TOP AND BATHROOM RECEPTACLES MUST BE
 GFCI PROTECTED. NEC 210.8
 NEW RECEPTACLES MUST BE TAMPER RESISTANT NEC 406.11
 BATHROOMS REQUIRE DEDICATED 20 AMP BRANCH CIRCUITS. NEC
 210-11(C)(3)
 A BONDING STRIP IS REQUIRED AT SERVICE GROUND NEC
 250.94
 GFCI PROTECTED RECEPTACLES ARE REQUIRED AT FRONT AND
 REAR ELEVATIONS. NEC 210.8
 AN ELECTRICAL RISER WITH PANEL SCHEDULE AND LOAD
 CALCULATION IS REQUIRED IF THE HOME IS BEING REWIRED.
 SHOW SERVICE AND PANEL BOARD LOCATIONS. NEC 215.15
 IF THE SCOPE OF RECONSTRUCTION INCLUDES AN ELECTRICAL
 CONNECTION TO THE GARAGE FROM THE HOUSE THAN A SPECIFIC
 WIRING METHOD IS REQUIRED. NEC 250.32
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  