| Plan Review Notes For Permit 11080670 |
| Permit Number |
11080670 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-08-25 14:34:21 | 4050 NORTH FLAGLER DRIVE | | | PERMIT #11080670 | | | MASTER #11080115 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | SUBMIT COPY OF SIGNED CONTRACT INDICATING THE TOTAL | | | COST (MATERIALS PLUS LABOR). | | | | | | INSPECTOR'S NOTE: | | | 1) A MANUAL ACTIVATION DEVICE SHALL BE LOCATED ALONG | | | THE EGRESS PATH AND BE A MINIMUM OF 10 FEET AND A | | | MAXIMUM OF 20 FEET FROM THE KITCHEN EXHAUST SYSTEM. THE | | | DEVICE SHALL BE MOUNTED 42-48 INCHES ABOVE THE FLOOR | | | AND SHALL CLEARLY IDENTIFY THE HAZARD PROTECTED PER FBC | | | 904.11.1. | | | | | | 2) DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE | | | HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE | | | THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT | | | TEMPERATURE REACHES 475F DEGREES AT 1 INCH BELOW THE | | | SURFACE. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|