| Date |
Text |
| 2011-08-30 09:49:09 | 1450 CENTREPARK BOULEVARD - SUITE #150 |
| | PERMIT #11080665 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE |
| | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING |
| | FIRE/SMOKE BARRIER - PROTECT ALL OPENINGS. CHARACTERS |
| | SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN |
| | STROKE. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 |
| | FEET ON CENTER. |
| | |
| | PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL |
| | BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. |
| | |
| | PROVIDE TACTILE SIGNAGE AT REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | SHEET A-8: THE COMMON PATH OF TRAVEL INDICATED ON THE |
| | PLAN EXCEEDS 100 FEET OF LENGTH. |
| | |
| | SHEET A-8: TRAVEL DISTANCE TO EXTINGUISHERS EXCEED 75 |
| | FEET. |
| | |
| | SHEET E-2: CONFERENCE ROOM #103 AND RECEPTION #101 |
| | EQUIPPED WITH CARD READERS PREVENTING OCCUPANTS FREE |
| | EGRESS TO A SECONDARY EXIT. |
| | |
| | SHEET E-2: EXIT ACCESS CORRIDOR IN SUITE #150 EQUIPPED |
| | WITH CARD READER ON EGRESS SIDE OF EXTERIOR EXIT DOOR. |
| | |
| | SHEET E-2: FOUR FIRE ALARM HORN-STROBE DEVICES SHOWN. |
| | IT MAY BE DIFFICULT TO MEET THE AUDIBILITY REQUIREMENTS |
| | OF NFPA 72 WITH ONLY FOUR AUDIBLE DEVICES. |
| | |
| | SHEET E-3: NO EXIT SIGNAGE PROVIDED FOR SOUTH OFFICE |
| | SPACE IN SUITE #165. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | |