| 2011-08-25 13:40:51 | 1 NORTH CLEMATIS STREET - SUITE #320 | | | PERMIT #11080627 | | | MASTER #11060068 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE ACTUAL MEASUREMENT BETWEEN THREE SEPARATE | | | SPRINKLERS EXCEEDS 15'-0". | | | | | | VERIFY THE THREE ROOMS TO THE EAST HAVE PROPER | | | SPRINKLER COVERAGE AS THE EXISTING SPRINKLERS ARE | | | LOCATED MORE THAN 9'-0" FROM WALLS. THESE ROOMS ARE | | | LABELED AS "NO CHANGE AFFECTING SPRINKLERS IN THIS | | | ROOM." | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|