| Plan Review Notes For Permit 11080604 |
| Permit Number |
11080604 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-09-06 15:29:46 | 3501 ELECTRONICS WAY - PHASE 2 | | | PERMIT #11080604 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | INDICATE THE TYPE OF RACK TO BE USED PER NFPA 13 | | | DEFINITIONS (DOUBLE-ROW RACK, MULTIPLE ROW RACK ETC.). | | | | | | INDICATE IF ANY SOLID SHELVING IS INTENDED TO BE USED | | | WITH THE RACK STORAGE. | | | | | | PER NFPA 13 SECTION 12.1.13.2 STANDARD RESPONSE | | | SPRINKLERS WITH A NOMINAL K-FACTOR OF 8.0 OR LARGER | | | SHALL BE USED FOR SPRINKLER DENSITIES BETWEEN 0.20 AND | | | 0.34 GPM/SQ.FT. | | | | | | PER NFPA 13 SECTION 12.3.1.14.1 A NOMINAL 6-INCH | | | TRANSVERSE FLUE SPACE IS REQUIRED BETWEEN LOADS AND | | | RACK UPRIGHTS. | | | | | | PER NFPA 13 SECTION 12.3.4.1.3 THE DISTANCE BETWEEN | | | AISLES SHALL BE AT LEAST 4-FEET. | | | | | | FIRE ALARM PLANS NOT SIGNED/SEALED BY ENGINEER. | | | | | | NOTE: SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER | | | SYSTEM AND/OR FIRE ALARM SYSTEM. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|