Plan Review Notes
Plan Review Notes For Permit 11080604
Permit Number 11080604
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-09-06 15:29:463501 ELECTRONICS WAY - PHASE 2
 PERMIT #11080604
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 INDICATE THE TYPE OF RACK TO BE USED PER NFPA 13
 DEFINITIONS (DOUBLE-ROW RACK, MULTIPLE ROW RACK ETC.).
  
 INDICATE IF ANY SOLID SHELVING IS INTENDED TO BE USED
 WITH THE RACK STORAGE.
  
 PER NFPA 13 SECTION 12.1.13.2 STANDARD RESPONSE
 SPRINKLERS WITH A NOMINAL K-FACTOR OF 8.0 OR LARGER
 SHALL BE USED FOR SPRINKLER DENSITIES BETWEEN 0.20 AND
 0.34 GPM/SQ.FT.
  
 PER NFPA 13 SECTION 12.3.1.14.1 A NOMINAL 6-INCH
 TRANSVERSE FLUE SPACE IS REQUIRED BETWEEN LOADS AND
 RACK UPRIGHTS.
  
 PER NFPA 13 SECTION 12.3.4.1.3 THE DISTANCE BETWEEN
 AISLES SHALL BE AT LEAST 4-FEET.
  
 FIRE ALARM PLANS NOT SIGNED/SEALED BY ENGINEER.
  
 NOTE: SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  