| Plan Review Notes For Permit 11080582 |
| Permit Number |
11080582 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-08-24 08:57:25 | 1 NORTH CLEMATIS STREET - SUITE #400 | | | TRACKING #11080582 | | | PERMIT #11070543 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVIDE SPRINKLER PROTECTION IN SMALL CLOSET LOCATED IN | | | CONFERENCE ROOM #415 AND OFFICE #414. | | | | | | VERIFY SPRINKLER COVERAGE BELOW HARD CEILING AREAS IN | | | CONFERENCE ROOM #415 AS NO CEILING ELEVATIONS PROVIDED | | | ON PLAN. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|