Plan Review Notes
Plan Review Notes For Permit 11080548
Permit Number 11080548
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-08-25 12:03:242400 METROCENTRE BOULEVARD EAST
 PERMIT #11080548
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISIONS*****
  
 THE PROPERTY APPRAISER INDICATES THIS BUILDING'S
 ADDRESS IS 2400. THE BUILDING ADDRESS 2410 IS INDICATED
 ON THE PERMIT APPLICATION AND PLANS.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 PROVIDE STROBE DEVICE IN LIBRARY ROOM AND VENDING ROOM.
  
 NO HEAT DETECTOR (OR FLOW SWITCH WITHOUT TIME DELAY)
 PROVIDED IN ELEVATOR MACHINE ROOM TO SHUNT TRIP POWER
 BEFORE APPLICATION OF WATER BY AUTOMATIC SPRINKLERS.
  
 PROVIDE A PRE-RECORDED FIRE ALARM EVACUATION MESSAGE
 NOTIFYING OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN
 THE BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE
 BUILDING IMMEDIATELY. DO NOT USE THE ELEVATOR.
  
 PER LOCAL CODE AMENDMENTS, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  