| 2011-08-19 14:08:35 | 1411 NORTH FLAGLER DRIVE - SUITE #9200 | | | PERMIT #11080527 | | | MASTER #11050760 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PLAN ADDRESS DOES NOT MATCH THE APPLICATION ADDRESS. | | | | | | FOR IDENTIFICATION PURPOSES, ASSIGN A NUMBER TO EACH | | | FIRE ALARM DEVICE ON THE SYSTEM. | | | | | | NO BATTERY CALCULATIONS SUBMITTED. | | | | | | NO STROBE DEVICES PROVIDED IN PATIENT BLOOD DRAW ROOMS. | | | | | | NO WIRE SIZE INDICATED ON THE PLANS. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | | | | | | | | | | |
|