 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLAN ADDRESS DOES NOT MATCH THE APPLICATION ADDRESS.
  
 FOR IDENTIFICATION PURPOSES, ASSIGN A NUMBER TO EACH
 FIRE ALARM DEVICE ON THE SYSTEM.
  
 NO BATTERY CALCULATIONS SUBMITTED.
  
 NO STROBE DEVICES PROVIDED IN PATIENT BLOOD DRAW ROOMS.
  
 NO WIRE SIZE INDICATED ON THE PLANS.
  